Conditions Of Crank Disconnect - Smartgen HGM400N Series User Manual

Genset controller
Hide thumbs Also See for HGM400N Series:
Table of Contents

Advertisement

7.5

CONDITIONS OF CRANK DISCONNECT

No.
0
Magnetic pickup
1
Generator frequency
2
Magnetic pickup + Generator frequency
3
Magnetic pickup + Oil pressure
4
Generator frequency + Oil pressure
5
Generator frequency + Magnetic pickup + Oil pressure
6
Oil pressure
1)
There are 3 conditions to make starter separated with engine; magnetic pickup, generator frequency
and oil pressure, which can be used separately, but oil pressure is suggested to be used together with
magnetic pickup and generator frequency. The aim is to disconnect the starter motor as soon as
possible.
2)
Magnetic pickup is the magnetic equipment installed in starter for detecting flywheel teeth.
3)
When magnetic pickup is selected, please ensure the number of flywheel teeth is the same as setting,
otherwise, "over speed shutdown" or "under speed shutdown" may be caused.
4)
If genset without magnetic pickup, please don't select corresponding items, otherwise, "start fail" or
"loss speed signal" may be caused.
5)
If genset without oil pressure sensor, please don't select corresponding items.
6)
If generator frequency is not selected in crank disconnect settings, controller will not collect and
display the relative power quantity (can be used in water pump set); if magnetic pickup is not selected
in crank disconnect setting, the engine speed displayed in controller is calculated by generator signal.
HGM400N Series Genset Controller User Manual
Table 11 Crank Disconnect Conditions
Content
Page 29 of 38

Hide quick links: