PARAMETER SETTING

8.1
PARAMETER SETTING
Start the controller, then press
1.
Set Parameters
2.
Information
3.
Language
4.
Event Log
5.
Maintenance Setting
Password "0318" can allow to set all items in Table 7 during inputting password. When default
password (0318) is changed, it needs to input the same password as controller for parameter setting
via PC software. If more parameter items are needed to set or password is forgotten, such as voltage
and current calibration, please contact with the factory.
:
NOTES
1)
HGM410N doesn't have items 1-5 in Table 7; programmable outputs 1-4 don't have digital outputs about mains.
2)
Please modify the parameters in standby mode (crank conditions, auxiliary input and output configuration, multi
delays, etc.) otherwise shutdown alarm or other abnormal conditions may appear.
3)
The over-voltage threshold must be greater than the under-voltage threshold; otherwise over-voltage and
under-voltage may occur at the same time.
4)
The over-speed threshold must be greater than under-speed threshold, otherwise over speed and under speed may
occur at the same time.
5)
Set frequency value (after crank disconnect) as low as possible, in order to disconnect starter quickly.
6)
Digital inputs 1-4 cannot be set to the same items, otherwise it cannot realize correct function; programmable
outputs 1-5 can be set as the same item.
7)
Digital input 3 can be configured as Fuel Level Sensor. Digital input 4 can be configured as Temperature Sensor, Oil
Pressure Sensor and Water Level Sensor. Digital input and sensor can be selected for any one: if input
configuration is chosen, the corresponding digital input parameter is active and the sensor parameter is inactive
but saved; on the contrary, if sensor is chosen, the corresponding sensor parameter is active and the digital input
parameter is inactive but saved.
8)
If it needs to shut down after cooling, please set any input as "stop after cooling" item, then connect this input to
ground; or set high temperature stop action as "cooling stop".
8.2

CONTROLLER INFORMATION

a)
On this page it will display information of controller, such as software version, hardware version,
issue date.
b)
NOTE: Press
c)
LCD contrast adjustment.
Press
and
(or
characters clearer. Adjustment range is 0-7.
HGM400N Series Genset Controller User Manual
to enter into the parameters setting menu as below:
and it will display the status of digital inputs and outputs.
and
) simultaneously and it can adjust LCD contrast and make LCD
Page 30 of 38