No.
Items
8
Gen Under Voltage
9
Gen Over Current
10
Fail to Start
11
High Temp.
12
Low Oil Pressure
13
No Gens
14
Low Fuel Level
15
Low Coolant Level
16
Temp. Sensor Open
17
OP Sensor Open
Fuel Level Sensor
18
Open
Temp.
Sensor
19
Open
20
OP Sensor 2 Open
21
Coolant
Level If the config. sensor set as level sensor, when the controller detects that the
HGM400N Series Genset Controller User Manual
When the controller detects that the genset voltage has fallen below the
pre-set value, it will initiate a shutdown alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that the genset current has exceeded the
pre-set value and delay is not 0, it will initiate a shutdown alarm and the
corresponding alarm information will be displayed on LCD.
If the engine does not fire after the pre-set number of attempts, it will initiate
a shutdown alarm and the corresponding alarm information will be
displayed on LCD.
When controller detects that the water/cylinder temperature has exceeded
the pre-set value, it will initiate a shutdown alarm and the corresponding
alarm information will be displayed on LCD.
When the controller detects that the oil pressure has fallen below the pre-set
value, it will initiate a shutdown alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that the genset frequency is 0, it will initiate a
shutdown alarm and the corresponding alarm information will be displayed
on LCD.
When the controller detects that the fuel level has fallen below the pre-set
value or detects that the low fuel level input is active, it will initiate a
shutdown alarm and the corresponding alarm information will be displayed
on LCD.
When the controller detects the low coolant level input is active, it will
initiate a shutdown alarm and the corresponding alarm information will be
displayed on LCD.
When the controller detects that the temperature sensor is open circuit and
the action selects "Shutdown", it will initiate a shutdown alarm and the
corresponding alarm information will be displayed on LCD.
When the controller detects that the oil pressure sensor is open circuit and
the action selects "Shutdown", it will initiate a shutdown alarm and the
corresponding alarm information will be displayed on LCD.
When the controller detects that the level sensor is open circuit and the
action selects "Shutdown", it will initiate a shutdown alarm and the
corresponding alarm information will be displayed on LCD.
If the config. sensor set as temperature sensor, when the controller detects
2
that the temperature sensor is open circuit and the action selects
"Shutdown", it will initiate a shutdown alarm and the corresponding alarm
information will be displayed on LCD.
If the config. sensor set as oil pressure sensor, when the controller detects
that the oil pressure sensor is open circuit and the action selects
"Shutdown", it will initiate a shutdown alarm and the corresponding alarm
information will be displayed on LCD.
Description
Page 14 of 38