Smartgen HGM400N Series User Manual page 17

Genset controller
Hide thumbs Also See for HGM400N Series:
Table of Contents

Advertisement

Pin
Function
7
Digital Input 1
8
Digital Input 2
9
Digital Input 3
10
Digital Input 4
11
Engine Temp. Sensor
12
Oil Pressure Sensor
13
Current IA
14
Current IB
15
Current IC
16
Current COM
17
Magnetic Pickup
18
Charger D+
19
Aux. Output 4
20
Aux. Output 5
21
Aux. Output COM
22
Gen AC Voltage U
23
Gen AC Voltage V
24
Gen AC Voltage W
25
Gen N2
26
Mains AC Voltage R
27
Mains AC Voltage S
28
Mains AC Voltage T
29
Mains N1
NOTE: USB interface is parameter programmable interface, which can be programmed on PC.
HGM400N Series Genset Controller User Manual
Cable Size
2
1.0mm
Ground connected is active (B-)
2
1.0mm
Ground connected is active (B-)
Ground connected is active (B-);
1.0mm
2
Can be used as Level Sensor.
Ground connected is active (B-);
1.0mm
2
Can be used as Config. Sensor.
Connect
2
1.0mm
temperature resistance sensor.
Connect
1.0mm
2
resistance sensor.
Outside connected to secondary coil of current
2
1.5mm
transformer (rated 5A).
Outside connected to secondary coil of current
1.5mm
2
transformer (rated 5A).
Outside connected to secondary coil of current
2
1.5mm
transformer (rated 5A).
2
1.5mm
See INSTALLATION in this manual.
Connect to speed sensor; Shielded wire is
0.5mm
2
recommended.
The other end of speed sensor connects to B-.
Connect to charging generator's D+ terminal. If
2
1.0mm
there is not this terminal, then hang it up.
The combination of terminal 19 and 21 is relay
1.0mm
2
normally open contact; rated 5A; Voltage free.
The combination of terminal 20 and 21 is relay
2
1.0mm
normally open contact; rated 5A; Voltage free.
1.5mm
2
Common terminal of auxiliary output 4 and 5.
Connected to U-phase of generator (2A fuse is
1.0mm
2
recommended).
Connected to V-phase of generator (2A fuse is
1.0mm
2
recommended).
Connected to W-phase of generator (2A fuse is
1.0mm
2
recommended).
1.0mm
2
Connected to N-wire of generator.
Connected to R-phase of mains (2A fuse is
2
1.0mm
recommended) (HGM410N without)
Connected to S-phase of mains (2A fuse is
1.0mm
2
recommended) (HGM410N without)
Connected to T-phase of mains (2A fuse is
1.0mm
2
recommended) (HGM410N without)
2
1.0mm
Connected to N-wire of mains (HGM410N without)
Description
For
please see Table
9.
to
water/cylinder
For
please see Table
to
oil
pressure
8.
set
items
set
items
Page 17 of 38

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm410nHgm420n

Table of Contents