Technical Data; Technical Data At A Glance - Endress+Hauser PROFIBUS Gammapilot M FMG60 Operating Instructions Manual

Radiometric measurement
Hide thumbs Also See for PROFIBUS Gammapilot M FMG60:
Table of Contents

Advertisement

Technical Data

Measured variable
Temperature input (PT 100)
for density measurements
Output signal
Output damping
Terminal voltage
Current consumption
Supply voltage
Power consumption
Overvoltage category
Protective class
90
10
Technical Data
10.1

Technical data at a glance

10.1.1
Input
The Gammapilot M measures the pulse rate (number of counts per second). This rate is proportional
to the intensity of radiation at the detector. From this rate, the Gammapilot M calculates the desired
measured value:
• Level limt (0% = "radiation path free"; 100% = "radiation path covered")
• Level (in %)
• Position of interface layer (in %)
• Density (unit selectable)
• Concentration (unit selectable)
In order to compensate temperature influences on the density measurements a temperature sensor
PT 100 (4-wire connection) can be connected.
• Measuring range: -40 °C ... 200 °C
• Accuracy: ±1 K
10.1.2
Output
• PROFIBUS PA
• Pulses for cascading mode
Freely selectable, 1 ... 999 s
10.1.3
Characteristics of the PROFIBUS PA interface
The following values are the voltages across the terminals directly at the instrument:
Type
standard
EEx ia (FISCO model
EEx ia (Entity concept)
11 mA ± 1 mA
10.1.4
Auxiliary energy
• 90 ... 253 V
; 50/60 Hz
AC
• 18 ... 36 V
; protected against polarity reversion
DC
• AC supply: approx. 8,5 VA
• DC supply: approx. 3,5 W
II
1
minimum terminal
maximum terminal
voltage
9 V
9 V
9 V
Gammapilot M FMG 60 - PROFIBUS PA
voltage
32 V
17,5 V
24 V