Gammapilot M FMG 60 - PROFIBUS PA
7.1.4
Error codes
Code
Description
A102
checksum error
W103
initialising
A106
downloading
A110
checksum error
A111
electronics defect
A113
electronics defect
A114
electronics defect
A116
download error
A121
electronics defect
W153
initialising
A160
checksum error
A165
electronics defect
A291
slave error
A503
wrong sensor type
W513
calibration integration running
W514
PT-100 calibration
A531
sensor electronics defect
A532
sensor voltage error
A533
wrong sensor software version
A535
sensor regulation error
W536
high voltage near limit
A538
sensor communication error
A602
linearisation table not plausible
A612
linearisation table not defined
W621
simulation on
A631
background not calibrated
A632
full/covered not calibrated
Remedy
call Endress+Hauser Service
wait for completion of the initialising procedure
wait for completion of the download
call Endress+Hauser Service
switch instrument off/on;
if error still is present:
call Endress+Hauser service or exchange transmitter
switch instrument off/on;
if error still is present:
call Endress+Hauser service or exchange transmitter
switch instrument off/on;
if error still is present:
call Endress+Hauser service or exchange transmitter
repeat download
switch instrument off/on;
if error still is present:
call Endress+Hauser service or exchange transmitter
wait for completion of the initialising procedure
call Endress+Hauser Service
switch instrument off/on;
if error still is present:
call Endress+Hauser service or exchange transmitter
check basic setup and connection of the slave tranmsitter
call Endress+Hauser Service
Wait, until a stable pulse rate has been reached; then, terminate
integration (by pressing "E" in the "average pulse rate" (*11)
function)
Wait for end of calibration;
if error persists: call Endress+Hauser Service
switch instrument off/on;
if error still is present:
call Endress+Hauser service or exchange transmitter
call Endress+Hauser Service
call Endress+Hauser Service
call Endress+Hauser Service
call Endress+Hauser Service
call Endress+Hauser Service
check monotony of the linearisation table; if necessary, adjust table
("linearisation" (*4) function group)
enter linearisation table
("linearisation" (*4)) function group
When entering via ToF-Tool:
make sure to use the right type of table (lin. table "level" or "concen-
tration")
Switch off linearisation
("output" (*6) function group
"simulation" (*65) function)
perform background calibration
("calibration" (*1) function group)
perform full/covered calibration
("calibration" (*1) function group)
Troubleshooting