Endress+Hauser PROFIBUS Gammapilot M FMG60 Operating Instructions Manual page 66

Radiometric measurement
Hide thumbs Also See for PROFIBUS Gammapilot M FMG60:
Table of Contents

Advertisement

Commissioning
ENDRESS + HAUSER
+
E
ENDRESS + HAUSER
+
E
ENDRESS + HAUSER
+
E
66
"Value full" (*14)
"Value empty" (*17)
Value full
*14
100%
Value empty
*17
0%
These functions are needed for level measurements only. They are used to specify the level at which
the full or empty calibration are performed.
Range of values
Value full (*14)
Value empty (*17)
"Calibration" (*15)
calibration
*15
stop/edit
start
This function is used to start the automatic entering of the selected calibration point.
Selection:
• stop/edit
This option must be selected, if
– the calibration point is not to be entered (e.g. because it has already been entered). The pulse
rate of the calibration point is then displayed in the following function, "full calibr." (*16) or
"empty calibr." (*17). I frequired, this value can be changed.
– the calibration point is to be entered manually. This can be done in the following function, "full
calibr." (*16) or "empty calibr." (*17).
• start
This option is used to start the automatic entering of the calibration point. After selecting this
option the Gammapilot M changes to the "avg. pulse rate" (*11) function.
Gammapilot M FMG 60 - PROFIBUS PA
minimum value
100%
60%
0%
0%
maximum value
100%
40%