Endress+Hauser PROFIBUS Gammapilot M FMG60 Operating Instructions Manual page 52

Radiometric measurement
Hide thumbs Also See for PROFIBUS Gammapilot M FMG60:
Table of Contents

Advertisement

Commissioning
52
"empty" or "free" calibration
(for details see Section 6.4.3, page 65)
Step
Function
1
2
Calibration point(*13)
the following function for level measurements only
3
Value empty (*17)
the following functions for level and limit measurements
4
Calibration (*15)
5
Average pulse rate (*11)
6
Calibration (*15)
7
empty calibration (*16)
8
next point (*19)
Calibration is thereby competed.
Gammapilot M FMG 60 - PROFIBUS PA
Action / Remarks
• Radiation remains switched on
• Empty the vessel
level: max. 40%
limit: radiation path free
Select "empty/free" by O or S;
confirm by F
enter current level (0% - 40%)
Select "start" by O or S;
confirm F
wait until value is stable;
then confirm by F
Select "stop/edit" by O or S;
confirm by F
Confirm value by F
Select "no" by O or S;
confirm by F.