Endress+Hauser PROFIBUS Gammapilot M FMG60 Operating Instructions Manual page 56

Radiometric measurement
Hide thumbs Also See for PROFIBUS Gammapilot M FMG60:
Table of Contents

Advertisement

Commissioning
ENDRESS + HAUSER
+
E
!
56
6.3.4
"Measuring mode" (*05)
meas. mode
*05
Âlevel
limit
density
This function is used to select the desired measuring mode.
Note!
The selection can be performed only once and the function is automatically locked after that. It can
only be unlocked again by a reset of the Gammapilot M ("Reset" (*A3) function).
(a)
(c)
Possible measuring modes of the Gammapilot M: a: a: a: a: level measurement (continuous); b: b: b: b: level limit detection; c: c: c: c: density
measurement (with temperature compensation if required); d: d: d: d: concentration measurement (density measurement
followed by linearisation)
Selection:
• level
• limit
• density (also with temperature compensation)
• concentration (density measurement followed by linearisation)
Gammapilot M FMG 60 - PROFIBUS PA
(b)
(d)
D
C
L00-FMG60xxx-05-00-00-xx-008