Endress+Hauser PROFIBUS Gammapilot M FMG60 Operating Instructions Manual page 51

Radiometric measurement
Hide thumbs Also See for PROFIBUS Gammapilot M FMG60:
Table of Contents

Advertisement

Gammapilot M FMG 60 - PROFIBUS PA
!
6.2.2
Calibration for level measurement and limit detection
Hinweis!
Basic principles of the calibration for level measurement and limit detection are described in
Section 6.4.1, page 60.
Background calibration
(for details see Section 6.4.2, page 63)
Step
Function
1
2
Background calibration (*10)
3
Average pulse rate (*11)
4
Background calibration (*10)
5
Background pulse rate (*12)
continue by full/covered and empty/free calibration
"full" or "covered" calibration
(for details see Section 6.4.3, page 65)
Step
Function
1
2
Calibration point (*13)
the following function for level measurements only
3
Value full (*14)
the following functions for level and limit measurements
4
Calibration (*15)
5
Average pulse rate (*11)
6
Calibration (*15)
7
full calibration (*16)
8
next point (*19)
go on to "empty" or "free" calibration
Action / Remarks
• Switch radiation off
• fill the vessel
for level: min. 60%
for limit: radiation path covered
Select "start" by O or S;
confirm by F
wait until value is stable;
then confirm by F
Select "stop/edit" by Oor S;
confirm by F
confirm value by F
Action / Remarks
• Switch on radiation
• Vessel remains filled.
Select "full/covered" by O or S;
confirm by F
enter current level (60% - 100%)
Select "start" by O or S;
confirm F
wait until value is stable;
then confirm by F
Select "stop/edit" by O or S;
confirm by F
Confirm value by F
select "yes" by O or S;
confirm by F.
Commissioning
51