6.3.5
"Density unit" (*06)
density unit
*06
Âg/cm3
g/l
lb/gal
This function is needed for density and concentration measurements only. It is used to select the
density unit.
Selection:
3
• g/cm
• g/l
3
• lb/gal; [1g/cm
= 8,345 lb/gal]
3
3
• lb/ft
; [1g/cm
= 62,428 lb/ft
• °Brix; [1°Brix = 270,4 (1 - 1/x)]
• °Baumé; [1°Baumé = 144,3 (1 - 1/x)]
• °API; [1°API = 131,5 (1,076/x - 1)]
• °Twaddell; [1°Twaddell = 200 (x-1)]
3
"x" ist the denisty in g/cm
. The formula gives the number of degrees corresponding to this density.
6.3.6
"Min. density" (*07)
min. density
*07
3
0,9500 g/cm
This function is needed for density and concentration measurements only. It is used to specify the
lower limit of the density range.
6.3.7
"Max. density" (*08)
max. density
*08
3
1,2500 g/cm
This function is needed for density and concentration measurements only. It is used to specify the
upper limit of the density range.