Radiometric measurement
Hide thumbs Also See for PROFIBUS Gammapilot M FMG60:
Table of Contents

Advertisement

Commissioning
ENDRESS + HAUSER
+
E
72
6.5.2
Background calibration
Excerpt from the operating menu
The following excerpt from the operating menu shows how the background calibration is entered.
The individual functions are explained in the sections below.
*10
backgr. calib.
0: stop/edit
1: start
0
"Background calibration" (*10)
backgr. calib.
*10
stop/edit
start
This function is used to start the background calibration
Selction:
• stop/edit
This option must be selcted if
– no background calibration is to be performed but the pulse rate of an existing background
calibration is to be displayed instead.
– a manual background calibration is to be performed.
After selecting this option, the Gammapilot M changes to the "bgr. pulse rate" (*12) function,
where the existing pulse rate is displayed and can be changed if required.
• start
This option is used to start an automatic background calibration. After selecting this option the
Gammapilot M changes to the "avg. pulse rate" (*11) function.
Gammapilot M FMG 60 - PROFIBUS PA
E
*11
*12
avg. pulse rate
bgr. pulse rate
1
-1: not calibrated
E
L00-FMG60xxx-05-00-00-en-044