Installation
1)
The weights of the various versions of the Gammapilot M are summarised in the section "Dimensions/Weight".
16
3.2.2
Installation conditions for level measurement
Conditions
• For level measurements the Gammapilot M is mounted vertically; if possible the detector head
should point downwards.
• The exit angle of the source container must be exactly aligned to the measuring range of the
Gammapilot M. Observe the measuring range marks of the Gammapilot M.
• In cascading mode no gap should occur between the measuring ranges of the different
Gammapilot M.
• The source container and the Gammapilot M must be mounted as close to the vessel as possible.
Any access to the beam must be blocked so that no persons or part of their body (hand, arm, head)
may come into the area of the beam.
• In order to enlarge the lifetime, the Gammapilot M should be protected against direct sun. If
necessary, a protective cover should be applied.
• The mounting device FHG60 (see chapter "Accessories)or an equivalent mounting device should
be used for fastening the Gammapilot M.
The mounting device must be installed in a way such that it can withstand the weight of the
1
Gammapilot M
under all operating conditions (e.g. vibrations).
Examples
1
3
1: 1: 1: 1: Vertical cylinder; the Gammapilot M is mounted vertically with the detector head pointing downwards; the gamma ray
is aligned to the measuring range. 2: 2: 2: 2: Cascading of multiple Gammapilot M; there is no gap between the measuring ranges.
3: 3: 3: 3: conical outlet (with protective cover); 4: 4: 4: 4: horizontal cylinder (with protective cover).
Gammapilot M FMG 60 - PROFIBUS PA
2
4
L00-FMG60xxx-17-00-00-xx-001