60 NONE – Start-up
Once communication between the drive and the adapter module is established, several
configuration parameters are copied to the drive. These parameters are shown in the
tables below and must be checked first and adjusted where necessary. You can adjust
the parameters via a drive control panel or a PC tool.
Note:
Not all drives will display the descriptive names for the configuration parameters.
The new parameter settings take effect only when you power up the module the
next time or when you activate the fieldbus adapter refresh parameter.
Use the NONE protocol selection when no fieldbus protocol is required. For
example, when only the Ethernet tool network is used or for synchronizing time.
FMBT-21 configuration parameters – group A (group 1)
Note: The actual parameter group number depends on the drive type. Group A (group
1) corresponds to:
parameter group 51 in ACS380, ACS480, ACH580, ACQ580 and ACS580.
parameter group 51 in ACS880 if the adapter is installed as fieldbus adapter A or
group 54 if the adapter is installed as fieldbus adapter B.
No.
Name/Value
01
FBA TYPE
02
Protocol/Profile
0 = Modbus/TCP
200 = NONE
03
Commrate
0 = Auto
1 = 100 Mbps FD
2 = 100 Mbps HD
3 = 10 Mbps FD
4 = 10 Mbps HD
04
IP configuration
0 = Static IP
1 = Dyn IP DHCP
Description
Read-only. Shows the fieldbus adapter type as de-
tected by the drive. The value cannot be adjusted
by the user.
If the value is 0 = None, the communication between
the drive and the module has not been established.
Selects the application protocol and communication
profile for the network connection.
The selections available for NONE protocol are lis-
ted below.
ABB Drives profile - Classic
NONE protocol
Sets the bit rate for the Ethernet interface.
Autonegotiate
100 Mbps, full duplex
100 Mbps, half duplex
10 Mbps, full duplex
10 Mbps, half duplex
Sets the method for configuring the IP address,
subnet mask and gateway address for the module.
Configuration is obtained from parameters 05...13.
Configuration is obtained via DHCP.
Default
Modbus/TCP
0=Modbus/TCP
0 = Auto
1 = Dyn IP DHCP