32 Modbus/TCP – Start-up
No.
Name/Value
Description
33
FBA A/B appl
Read-only. Displays firmware version of the adapter module in
SW ver
xxyy format, where:
xx = major revision number
yy = minor revision number
Example: 310 = 3.10
Version number is the form:
<major>.<minor>.<patch>.<build>
Example: 3.10.200.13 or 3.10.0.0
Application program revision of the adapter module
1) 6-digit register addressing (400001) is used instead of 5-digit register addressing (40001) to describe register
map.
2) Register address = Register address + 40000 (0) if holding register area indication should be used.
For more information, see
Register addressing (page 47)
FMBT-21 configuration parameters – group B (group 2)
Note: The actual parameter group number depends on the drive type. Group B (group
2) corresponds to:
parameter group 53 in ACS380, ACS480, ACS580, ACH580, and ACQ580
parameter group is typically 53/56 (group 153/156 in some variants) in ACS880
if the adapter is installed as fieldbus adapter A/B.
Name/Value
Description
No.
1)
01
FBA A/B data
Selects the drive parameter address into which the value of the
out1 (client to
Data out 1 register is written (from the client to the server). The
drive)
Modbus register address maps are explained in chapter
bus/TCP – Communication
decimal number in the range of 0 to 9999 as follows:
0
1...99
101...9999
0 = None
Not used
101...9999
Parameter index with format xxyy, where
• xx is the parameter group number (1...99)
• yy is the parameter number index within
that group (01...99).
Note: In ACS480, ACS580 and ACS880, choose Other to display a
list of mappable drive parameters.
02 ...
Data out 2 ...12
See parameter 01 FBA A/B data out1.
12
1) The number of parameters in this group may vary by drive type and drive firmware.
protocolThe content is defined by a
Not used
Virtual address area of drive control. Not used
when the Modbus/TCP protocol is used.
Parameter area of the drive
Default
N/A
Default
0 = None
Mod-
0 = None

Advertisement