Sntp Time Offset To Utc Time; Drive Electronic Serial Number; Exception Codes; Communication Profiles - ABB FMBT-21 User Manual

Modbus/tcp adapter module
Table of Contents

Advertisement

Object ID
80h

Drive electronic serial number

SNTP time offset to UTC time

Register address
(4)00084
Drive electronic serial number
Register address
(4)60000...(4)60039

Exception codes

The adapter module supports the Modbus exception codes shown below.
Exception Code
Name
01h
ILLEGAL FUNCTION
02h
ILLEGAL DATA ADDRESS
03h
ILLEGAL DATA VALUE
04h
SLAVE DEVICE FAILURE
06h
SLAVE DEVICE BUSY

Communication profiles

Modbus is an application layer messaging protocol. It describes how data is transferred
between the client and a server, but not the meaning of that data. Communication
profiles are used to define the meaning of the data.

ABB Drives profile - Classic

The ABB Drives profile - Classic communication profile provides register mapped
access to the control, status, reference and actual values of the ABB Drives profile in
the classic format for backward compatibility.
Modbus/TCP – Communication protocol 49
Description
Time in minutes to offset the UTC
time received from the SNTP.
Description
(4)60000 Drive electrical serial number, most signi-
ficant character
...
(4)60039 Drive electrical serial number, least signi-
ficant character
Name
Value
-1440...1440 minutes
Description
The function code received in the query is
not an allowable action for the server.
The data address received in the query is to
an allowable address for the server.
A value contained in the query data field is
not an allowable value for the server.
An unrecoverable error occurred while the
server was attempting to perform the re-
quested action.
The server is engaged in processing a long-
duration command. The client should re-
transmit the message later when the server
is free.