ABB FMBT-21 User Manual page 68

Modbus/tcp adapter module
Table of Contents

Advertisement

68 NONE – Diagnostics
Name
Color
HOST
Flashing green
Green
Flashing red
Flashing orange, al-
ternating with the
MODULE flashing
orange
MODULE
Off
Flashing orange
Orange
Green
Flashing red
Red
Flashing orange, al-
ternating with the
HOST flashing or-
ange
NETWORK /
Off
NET
Flashing green
Flashing orange
Function
Establishing communication to drive
Connection to drive OK
Communication to drive lost temporarily
Internal file system error. The error may be cleared by cycling drive
power. If the error persists, contact your local ABB representative.
There is no PC tool connected to the device.
Device is attempting to obtain IP configuration from the DHCP
server.
Device is executing Duplicate Address Detection.
PC tool is connected to the device.
Ethernet link is down.
Ethernet interface is disabled. Duplicate Address Detection may
have detected a duplicate address. Check the IP configuration and
either initiate a Fieldbus Adapter parameter refresh or cycle power
to the drive.
Internal file system error. The error may be cleared by cycling drive
power. If the error persists, contact your local ABB representative.
Ethernet link is down.
Ethernet link is up at 100 Mbps.
Flashing indicates activity on interface.
Ethernet link is up at 10 Mbps.
Flashing indicates activity on interface.