4.3.

Analog Input Telegram

All analog input telegram data values are represented as 16-bit values.
To read the analog input telegram, use Modbus function code 3
Read Holding Registers or 4 Read Input Registers.
Address for data access to device connected to port
1
2000h
2001h
2002h
2003h
2004h
2005h
2006h
2007h
2008h
2009h
200Ah
4.4.

Parameters

The MTQ22-FBP does not support reading or writing PSE softstarter parameters such as
start ramp time, initial voltage and torque control.
4.5.

Diagnostics

To read the diagnostics data, use Modbus function code 3
Read Holding Registers or 4 Read Input Registers. The following chapter presents register
values associated to diagnostic data for both PSE and MTQ-FBP devices.
STATUS
Approved
© Copyright 2019 ABB. All rights reserved.
2
3
2100h
2200h
2101h
2201h
2102h
2202h
2103h
2203h
2104h
2204h
2105h
2205h
2106h
2206h
2107h
2207h
2108h
2208h
2109h
2209h
210Ah
220Ah
SECURITY LEVEL
Public
Data
4
2300h
Motor current in
% of Ie (0%-
800%)
2301h
Thermal load in
% of trip tem-
perature (0%-
100%)
2302h
Phase current L1
2303h
Phase current L2
2304h
Phase current L3
2305h
Max phase cur-
rent
2306h
Measured fre-
quency
2307h
Measured power
factor
2308h
Output voltage
in % of line volt-
age
2309h
Counted number
of starts
230Ah
Run time in
hours
DOCUMENT ID.
1SFC132374M0201
F I ELD BU S CO MMU N ICAT ION
Representa-
Value = 1 ⇒ 1%
tion
Value = 1 ⇒ 1%
Value = 1 ⇒ 1A
Value = 1 ⇒ 1A
Value = 1 ⇒ 1A
Value = 1 ⇒ 1A
Value = 1 ⇒ 1Hz
Value = 100 ⇒ 1
Value = 1 ⇒ 1%
Value = 1 ⇒ 100
Value = 1 ⇒ 10h