Output data
Reference 2 (Not used)
1)
Constant frequency 1
1)
Constant frequency 2
1) Example
The table below gives the recommended drive parameter settings.
Drive parameter)
50.01 FBA A enable
50.02 FBA A comm loss func
50.03 FBA A comm loss t out
50.04 FBA A ref1 type
51.01 FBA A type
51.02 Protocol/Profile
51.03 Commrate
51.04 IP configuration
51.05 IP address 1
51.06 IP address 2
51.07 IP address 3
51.08 IP address 4
51.09 Subnet CIDR
51.20 Timeout time
51.21 Timeout mode
52.01 FBA A data in1
Modbus register
Input data
(4)00003
Actual value 2 (Not used)
(4)00004
Power
(4)00005
(4)00006
DC bus voltage
(4)00007
Setting for ACS480 and ACS580
drives
1 = Enable
1)
1 = Fault
1)
3.0 s
0 = Speed or frequency
2)
Modbus/TCP
1 = MB/TCP ABB E
1)
0 = Auto
1)
0 = Static IP
1)
192
1)
168
1)
0
1)
16
1)
24
1)
10
1)
2 = Control RW
1)
01.14
Modbus/TCP – Start-up 35
Modbus register
(4)00053
1)
(4)00054
(4)00055
1)
(4)00056
(4)00057
Description
Enables communication between
the drive and the fieldbus adapter
module.
Enables fieldbus A communica-
tion fault monitoring.
Defines the fieldbus A communic-
ation break supervision time.
Selects the fieldbus A reference 1
type and scaling.
Displays the type of the fieldbus
adapter module.
Selects the Modbus/TCP protocol
and the ABB Drives - Enhanced
profile.
Ethernet communication rate is
negotiated automatically by the
device.
Configuration will be obtained
from parameters 05...13.
First part of the IP address
Second part of the IP address
Third part of the IP address
Last part of the IP address
Sets the network mask as
255.255.255.0, allowing access
only to the last subnet.
Sets the communication timeout
as 1 second.
The timeout feature monitors the
updating of the Control word and
Reference 1.
Output power
12