36 Modbus/TCP – Start-up
Drive parameter)
52.03 FBA a data in3
53.01 FBA A data out1
53.03 FBA A data out3
51.27 FBA A par refresh
20.01 Ext1 commands
22.11 Speed ref1 source
31.11 Fault reset selection
1) Example
2) Read-only or automatically detected/set
The start sequence for the parameter example above is given below.
Control word:
Reset the fieldbus communication fault (if active).
Enter 47Eh (1150 decimal) -> READY TO SWITCH ON.
Enter 47Fh (1151 decimal) -> OPERATING (Scalar motor control mode).
Parameter setting examples – ACS880
Speed control using the ABB Drives – Enhanced communication profile
This example shows how to configure a speed control application that uses the ABB
Drives - Enhanced profile. In addition, some application-specific data is added to the
communication.
The start/stop commands and reference are according to the ABB Drives profile. For
more information, see section
When Reference 1 (REF1) is used, a reference value of ±20000 (4E20h) corresponds to
the reference set with parameter 46.01 Speed scaling in the forward and reverse
directions.
The minimum and maximum 16-bit integer values that can be given through the fieldbus
are -32768 and 32767 respectively.
Output data
Control word
Speed reference
Reference 2 (Not used)
Setting for ACS480 and ACS580
drives
1)
01.11
1)
28.26
1)
28.27
1 = Refresh
12 = Fieldbus A
4 = FB A ref1
06.1.7
ABB Drives communication profile (page
Modbus register
Input data
(4)00001
Status word
(4)00002
Speed actual value
(4)00003
Actual value 2 (Not used)
Description
DC voltage
Constant frequency 1
Constant frequency 2
Validates the FMBT-21 configura-
tion parameter settings.
Selects the fieldbus A interface as
the source of the start and stop
commands for external control
location 1.
Selects the fieldbus A reference 1
as the source for speed reference
1.
Selects the fieldbus interface as
the source for the fault reset sig-
nal.
40).
Modbus register
(4)00051
(4)00052
(4)00053