64 NONE – Start-up
No.
Name/Value
31
D2FBA A/B comm
status
0 = Idle
1 = Exec.init
2= Time out
3= Conf.err
4 = Off-line
5 = On-line
6 = Reset
32
FBA A/B comm SW
ver
33
FBA A/B appl SW ver

Starting up fieldbus communication

1.
Power up the drive.
2.
Enable communication between the adapter module and the drive by selecting
the correct slot number in parameter 50.01 FBA A enable.
The selection must correspond to the slot where the adapter module is installed.
For example, if the adapter module is installed in slot 1, you must select slot 1.
3.
Set the module configuration parameters in group 51.
select the communication protocol and profile with parameter 51.02, and
configure the network settings with parameters 51.03...51.13.
Description
Read-only. Displays the status of the fieldbus ad-
apter module communication.
Note: The value names may vary by drive.
Adapter is not configured.
Adapter is initializing.
A timeout has occurred in the communication
between the adapter and the drive.
Adapter configuration error: The major or minor
revision code of the common program revision in
the fieldbus adapter module is not the revision re-
quired by the module or mapping file upload has
failed more than three times.
Adapter is off-line.
Adapter is on-line.
Adapter is performing a hardware reset.
Read-only. Displays patch and build numbers of
the adapter module's firmware version in xxyy
format, where:
xx = patch number
yy = build number.
Example: If the firmware version (<ma-
jor>.<minor>.<patch>.<build>) is 3.10.200.13, the
value C80D is displayed. If the version is 3.10.0.0,
the value 0 is displayed.
See also parameter 33.
Read-only. Displays major and minor revision
numbers of the adapter module's firmware version
in xxyy format, where:
xx = major revision number
yy = minor revision number
Example: If the firmware version (<ma-
jor>.<minor>.<patch>.<build>) is 3.10.200.13 or
3.10.0.0, the value 310 is displayed.
See also parameter 32.
Default
0 = Idle
or
4 = Offline
or
2 = Time out
N/A
N/A