5.1.2.3 RtyCnt value in the CLNROL-function
You can choose the RtyCnt value in the CLNROL-function. RtyCnt means the number of the
picking or putting error restoration in the transporter operation.
When the number of the picking or putting error restoration exceeds the set RtyCnt value, the
Alarm LED is blinking and "REQ CLNROL" message is displayed on the LCD.
5.1.2.4 Changing the RtyCnt value
Default RtyCnt value : 15
The procedure described below is the operation in case of changing the RtyCnt from default
value (=15) to 25.
Operation Example
Operation 1
Operation 2
Operation 3
Operation 4
Press the arrow key and select the Set ?.
Display (line 2): Set ?
Press the ENTER key and define the command.
Display (line 2): Disable?
Press the ENTER key and define the command.
Display (line 2): Complete
Switch ON the power and wait for the completion of power-on test.
Display: READY and DRV empty are alternately displayed.
Press the ENTER key.
Display: STATUS
Press the arrow key and select the MAINTENANC command
Display : MAINTENANC
Press the ENTER key and define the command.
Display (line 1): PASSWORD
Display (line 2): 0000000000