Decision-Makerr 6000 With Integral Voltage Regulator; Features; Specifications - Kohler Decision-Maker 1 Manual

Industrial generator sets
Table of Contents

Advertisement

1.10 Decision-Makerr 6000 with
Integral Voltage Regulator

1.10.1 Features

D
A digital display and keypad provide access to data.
A two- line vacuum fluorescent display provides
complete and concise information.
D
The controller provides built-in paralleling capabilities
for paralleling applications incorporating multiple
generator set and/or utility feeds.
D
The controller can communicate with a personal
computer directly or on a network. See spec sheet
6-76, Monitor III Software for more information.
G
D
Using optional menu-driven, Windowsr-based PC
software, an operator can monitor engine and
alternator parameters and also provide control
capability.
D
The controller supports Modbusr RTU (Remote
Terminal
Unit),
an
communication protocol.
Voltage Regulator Menu 11 Displays
D
Voltage adjust
d
Three-phase voltage display
d
Numeric entry of voltage adjust
D
Under frequency unload (V/Hz) settings
d
Enable/disable
d
Cut-in frequency
d
Numeric entry of V/Hz slope
D
Reactive droop settings
d
Enable/disable
d
Numeric entry of droop setting
D
Voltage regulator gain
D
Analog voltage adjust enable
Paralleling Menu 16 Displays
D
DPS system commissioning setup
d
Node ID
d
Number of nodes
D
Synchronizing parameters setup
d
Voltage matching
d
Frequency matching
d
Phase matching
d
Time delays
D
Synchronizing value metering
d
Phase rotation
d
Bus and generator voltages
d
Bus and generator frequencies
d
Phase difference
d
Speed and voltage bias output values
D
DPS system controls configuration
d
Select digital inputs or software overrides
24
Section 1 Specifications
industry
standard
open
Load Share Control Menu 17 Displays
D
Real power sharing and control setup
d
kW sharing settings
d
kW base load settings
d
kW droop settings
d
kW ramp settings
d
kW disconnect level
D
Reactive load sharing and control setup
d
kVAR sharing settings
d
kVAR control settings
d
Power factor control settings
d
Reactive droop settings
D
Circuit breaker control setup
d
Energize time
d
Reclose time delay
d
Maximum close attempts
d
Fault current settings (fail to open)
Modbusr is a registered trademark of Schneider Electric.
Windowsr is a registered trademark of Microsoft Corporation.

1.10.2 Specifications

Specifications/
Features
Generator Set Availability
Type
Status and Shutdown
Indicators
Operating Temperature
Storage Temperature
Humidity
Solid-State, Redundant Software and
Circuit Protection
Sensing, Nominal
Sensing Mode
Input Requirements
Continuous Output
Maximum Output
Transition Frequency
No-Load to Full-Load
Voltage Regulation
Thermal Drift
Response Time
System Voltage Adjust.
Voltage Adjustment
Remote Voltage
Adjustment
Reactive Droop plus Full Load Share
Paralleling Capability
VAR/PF Control Input
Voltage Regulator Type
Integral with DEC 6000
20--3250 kW
Microprocessor based
LEDs and Digital Display
--40_C to 70_C (--40_F to 158_F)
--40_C to 85_C (--40_F to 185_F)
5--95% Non-Condensing
Fuses
100--240 Volts (L-N), 50--60 Hz
RMS, Single- or 3-Phase
8--36 VDC
100 mA at 12 VDC
100 mA at 12 VDC
50--70 Hz
±0.25%
<0.5%
(--40_C to 70_C)
[--40_F to 158_F ] Range
Less Than 5μS
±10%
Controller Keypad
Digital Input Standard/
Analog 0--5 VDC Input Optional
and Control
Standard