Kohler Decision-Maker 1 Manual page 120

Industrial generator sets
Table of Contents

Advertisement

Refer
Status Event
to
or Fault
Menu
No Oil Pressure
10
Signal
Overcrank Shutdown
8, 10
Over Current
10
Over Current Voltage
Restraint Shutdown
(see SD Over
Current Voltage
Restraint)
Overfrequency
7, 10
Shutdown
Overpower
(see PR Over Power
or SD Over Power)
Over Speed
7, 10
Shutdown
Overvoltage
7, 8,
Shutdown
10
Password
(see Access Code)
PGEN
10, 16
Communication Not
Online
PR Loss of Field
10, 15
(signal)
PR Over Current
10, 15
Voltage Restraint
PR Over Frequency
10, 15
PR Over Power
10, 15
PR Overvoltage
10, 15
PR Reverse Power
10, 15
PR Under Frequency
10, 15
PR Under Voltage
10, 15
Remote Shutdown
9, 10
D15
Reverse Power
(see PR Reverse
Power or SD
Reverse Power)
SD Loss of Field
10, 15
(signal)
SD Over Current
10, 15
Voltage Restraint
SD Over Power
10, 15
SD Reverse Power
10, 15
Speed Sensor Fault
10
Starter 'A'
10
* DD/MTU engine with MDEC/ADEC
[ NFPA applications
Section 7 Decision-Makerr 6000 Controller
120
Relay
Driver
Output
(RDO)
Digital Display
NO OIL
PRESSURE
SIGNAL
OVER CRANK
(lead 12)
OVER
RDO-14
CURRENT
OVER
FREQUENCY
OVER SPEED
(lead 39)
OVER
(lead 26)
VOLTAGE
PGEN COMM
NOT ONLINE
PR LOSS OF
FIELD
PR OVER
CURRENT VR
PR OVER
FREQUENCY
PR OVER
POWER
PR OVER
VOLTAGE
PR REVERSE
POWER
PR UNDER
FREQUENCY
PR UNDER
VOLTAGE
REMOTE
SHUTDWN
SD LOSS OF
FIELD
SD OVER
CURRENT VR
SD OVER
POWER
SD REVERSE
POWER
SPEED
SENSOR
FAULT
STARTER 'A'
FAILURE
Default
Selection
Range Setting
Fixed
0--6 Cycles
3 Cycles
Fixed
110%
100%--140%
140% Std.
103% FAA
65--70 Hz (60 Hz)
70 (60 Hz)
55--70 Hz (50 Hz)
70 (50 Hz)
105%--135%
135%
of nominal
10-sec time
delay *
10%--100%
20%
5 sec. delay
100%--200%
175%
5 sec. delay
100%--140%
102%
5 sec. delay
90%--150%
110%
5 sec. delay
100%--130%
110%
5 sec. delay
0%--50%
10%
5 sec. delay
80%--100%
96%
5 sec. delay
70%--100%
90%
5 sec. delay
Fixed
0 sec.
inhibit,
0 sec. delay
10%--100%
100% 120
sec. delay
100%--200%
200% 120
sec. delay
90%--150%
150% 120
sec. delay
0%--50%
50%, 120
sec. delay
] 3x (times) energize time shown in Menu 17
Inhibit
Time
Time
Delay
User-Defined
Delay
Settings
(sec.)
(sec.)
30
4
Not adjustable
10
Not adjustable
10
0.25
2--10
Not adjustable
0--120
0--120
0--120
0--120
0--120
0--120
0--120
0--120
-
0--120
0--120
0--120
0--120
Not adjustable
Not adjustable
TP-6356 4/12