Calibration
kW sharing gain
kW sharing reset
kW sharing deadband
Frequency trim gain
Frequency trim deadband
kW base load adjustment
kW base load gain
kW baseload reset
kW base load deadband
% droop at rated kW
% kW ramp rate
% kW up/down rate
Disconnect
kVAR sharing gain
kVAR sharing reset
kVAR share deadband
Voltage trim gain
Voltage trim deadband
kVAR base load
Generate kVAR?
kVAR base load gain
kVAR base load reset
kVAR base load deadband
kVAR up/down rate
Power factor setting
Lagging power factor?
Power factor control gain
Power factor control reset
Power factor control
deadband
Power factor up/down rate
% voltage droop at rated
load
Breaker energize time delay
Breaker reclose time delay
Breaker close attempts
Circuit breaker current fault
limit
Circuit breaker current fault
time delay
Transformer phase shift
Section 7 Decision-Makerr 6000 Controller
122
Refer
to
Menu
Digital Display
17
KW SHARING GAIN
17
KW SHARING RESET
17
KW SHARING DB
17
FREQ TRIM GAIN
17
FREQ TRIM DB
17
KW BASELOAD ADJ
17
KW BASELOAD GAIN
17
KW BASELOAD RESET
17
KW BASELOAD DB
17
% DROOP AT RATED KW
17
% KW RAMP RATE
17
% KW UP/DOWN RATE
17
DISCONNECT
17
KVAR SHARING GAIN
17
KVAR SHARING RESET
17
KVAR SHARE DEADBAND
17
VOLTAGE TRIM GAIN
17
VOLT TRIM DEADBAND
17
KVAR BASELOAD
17
GENERATE KVAR?
17
KVAR BASELOAD GAIN
17
KVAR BASELOAD RESET
17
KVAR BASE DEADBAND
17
KVAR UP/DOWN RATE
17
PF SETTING
17
LAGGING PF?
17
PF CONTROL GAIN
17
PF CONTROL RESET
17
PF CONTROL DEADBAND
17
PF UP/DOWN RATE
17
% VOLTAGE DROOP AT
RATED LOAD
17
BREAKER ENERGIZE TD
17
BREAKER RECLOSE TD
17
BREAKER CLOSE
ATTEMPTS
17
CB CRNT FAULT LIMIT
17
CB CRNT FAULT TD
17
XFMR PHASE SHIFT
Range Setting
Default Selection
0--99.99
0--50 sec.
0--10%
0--99.99
0--10%
0--100%
0--99.99
0--50 sec.
0--10%
0--10%
0--25%/S
10.0%/sec.
0--25%/sec.
0--25%
0--99.99
0--50 sec.
0--10%
0--99.99
0--10%
0--100%
Generate/absorb
0--99.99
0--50 sec.
0--10%
0--100%
0.50--1.00 PF
Lagging/leading
0--99.99
0--50 sec.
0--0.1 PF
0--0.1 PF/S
0.001 PF/S
0--20%
0.1--10.00 sec.
0.5--30.00 sec.
1--100
1--50%
0--60 sec.
Fixed
User-Defined
Settings
1.00
50 sec.
1.0%
1.00
0.1%
50.0%
1.00
1.0 sec.
1.0%
5.0%
1.0%/sec.
5.0%
1.00
1.0 sec.
1.0%
1.00
1.0%
50.0%
Generate
1.00
1.0 sec.
1.0%
1.0%/sec.
0.80 PF
Lagging
1.00
1.0 sec.
0.01 PF
4.0%
0.5 sec.
2.0 sec.
3
5.0%
5.0 sec.
0.00 deg.