6. Install the application software (as needed).
a. Determine the application code version. Use
the procedure found in the generator set
operation manual for Menu 20, Factory Setup
information.
b. If the application code version is 2.21 or higher,
the software update is already done.
sensor installation is complete. Go to step 7.
If the application code version is less than
application code version 2.21, continue with the
software update.
MENU 20
FACTORY SETUP
FINAL ASSEMBLY DATE
DD/MM/YY
FINAL ASSEMBLY
CLOCK NO ?
OPERATING DAYS
MODEL NO
SPEC NO
GENSET SERIAL NO
ALTERNATOR PART NO
ENGINE PART NO
TEMP SENSOR
YES
GM31045- -X
SERIAL NO
CONTROLLER SERIAL NO
CODE VERSION
COPYRIGHT
XXXX
SETUP LOCKED
YES
Figure 5-12 Menu 20, Factory Setup
TP-6356 4/12
#
#
#
#
#
#
TEMP SENSOR
GM16787
#
#
c. Program loader and controller application
software files can be downloaded from the
KOHLERnet. Use your SecurID to access the
KOHLERnet and click on the TechTools button
to request and download the files. Use the
program loader instructions for completing the
application code upgrade.
The
7. Determine the appropriate temperature sensor
selection.
Change the temperature sensor selection using
the controller keypad.
a. Go to Menu 20, Factory Setup. The menu can
remain locked when changing the sensor
selection. See Figure 5-12.
NO
TEMP SENSOR
GM17362
NO
Section 5 Decision-Makerr 550 Controller
93