f. Unlock the setup.
D
Arrow down to the FINAL ASSEMBLY,
CLOCK NO. display.
number on the controller display.
D
Arrow right to ENTER CODE display.
D
Use the controller keypad to enter the clock
number previously recorded.
D
Press the ENTER key. Changes to Menu 20,
Factory Setup, are now possible.
g. Initialize the EEPROM.
D
Arrow down to the CODE VERSION display.
D
Arrow right to INITIALIZE EEPROM display.
D
Press the YES key to initialize the EEPROM.
D
Press the ENTER key.
h. Wait for completion of the system reset.
i. Go to Menu 20, Factory Setup. See Figure 5-7
or Figure 5-8 for displays.
j. Change the final assembly date.
D
Arrow down to the FINAL ASSEMBLY DATE
display.
D
Enter the final assembly date using the data
recorded from the old controller, reference
step 2.e. If data from the old controller is not
available, keep the default setting.
D
Press the ENTER key if making a new entry.
k. Change the final assembly clock number.
D
Arrow down to the FINAL ASSEMBLY
CLOCK NO. display.
D
Enter the final assembly clock number using
the data recorded from the old controller. If
data from the old controller is not available,
keep the default setting.
D
Press the ENTER key if making a new entry.
l. Change the serial number.
service replacement kit will show the GENSET
SERIAL NO. as 123456. After the personality
profile is loaded, the GENSET SERIAL NO.
shows the correct serial number for the
respective generator set. Use the GENSET
TP-6356 4/12
Record the clock
The controller
SERIAL NO. to update the SERIAL NO. display
as follows:
D
Arrow down to the SERIAL NO. display.
D
Enter the serial number of the generator set
using data recorded from the old controller or
as shown on the generator set nameplate. If
the serial number is six digits, enter a leading
zero for a seven-digit serial number.
D
Press the ENTER key. The GENSET S/N
WARNING display no longer appears when
the GENSET SERIAL NO. and SERIAL NO.
match.
12. Perform the Menu 13, Communications entries.
a. Press the RESET MENU key on controller
keypad.
b. Use the controller keypad to go to Menu 13,
Communications.
c. Complete the communication entries as
necessary for remote programming. Use the
information from the controller operation
manual as necessary.
13. Perform the Menu 14, Programming mode entries.
a. Press the RESET MENU key on controller
keypad.
b. Use the controller keypad to go to Menu 14,
Programming Mode, and select programming
mode—remote. Use the information from the
Monitor II software, version 4.0.0 or higher.
14. Perform the Menu 20, Factory Setup entries using
the Generator Info window. Use the information
from the Monitor II software, version 4.0.0 or
higher.
a. Change the model number.
D
Go to the MODEL NO. display.
D
Enter the model number using the data
recorded from the old controller or as shown
on the generator set nameplate.
b. Change the spec (specification) number.
D
Go to the SPEC NO. display.
D
Enter the spec number using the data
recorded from the old controller or as shown
on the generator set nameplate.
Section 5 Decision-Makerr 550 Controller