Function
Starting: Place the generator set master switch
in the RUN position or AUTO position with
contacts 3 and 4 closed. The generator set
master switch closes contacts between N
and 47.
Note: Fault shutdowns are inhibited during
startup until K3 energizes.
Running: Alternator winding V0--V7 (P1-12 and
P1-15) produces AC output.
Note: K3 relay must obtain AC output within
30 seconds or overcrank fault occurs.
Stopping: Place the generator set master
switch to the OFF position to open circuit
between N and 47.
Fault shutdowns: Low oil pressure (LOP), high
coolant temperature (HCT). Contacts close
5--8 seconds after reaching shutdown level.
Note: The fault shutdown latches (K5) to keep
the fault lamp lit. Move the generator set master
switch to OFF/RESET.
Fault shutdown: Overspeed (OS). Contacts
close when engine speed reaches shutdown
level.
Note: The fault shutdown latches (K5) to keep
fault lamp lit. Move the generator set master
switch to OFF/RESET.
Fault shutdown: Overcrank (OC). Contacts
close on overcrank (locked rotor) if the speed
sensor signal is absent longer than 30 seconds.
Note: The fault shutdown latches to keep the
fault lamp lit. Move the generator set master
switch to OFF/RESET.
Figure 2-2 Relay Controller Sequence of Operation
28
Section 2 Decision-Makerr 1 Troubleshooting
Relay Contact
Relay
Normal Position
K2
Open
K10
Open
K4
Open
K20
Open
K3
Closed
K4
Open
K2
Open
K1
Closed
K1
Closed
K1
Closed
Relay Contact
Action
Energizes/Action:
K2 relay and LED2 lights
K10 relay, engine components (fuel
system, governor, ignition, etc.), K4
Close
relay, and LED4 lights
Close
Hourmeter
Close
K20 relay
Starter solenoid (SS) relay and starter
Close
motor (SM)
K3 relay and LED3 lights
Deenergizes K4 relay and LED4
Open
deenergizes
Deenergizes starter solenoid (SS) and
Open
starter motor (SM)
Deenergizes K2 relay and LED2
deenergizes
Deenergizes engine components;
Open
generator set shuts down
K1 relay, LED1 lights, and fault lamp
Deenergizes engine components;
Open
generator set shuts down
K1 relay, LED1 lights, and fault lamp
Deenergizes engine components;
Open
generator set shuts down
K1 relay, LED1 lights, and fault lamp
Deenergizes engine components;
Open
generator set shuts down
TP-6356 4/12