Kohler Decision-Maker 1 Manual page 121

Industrial generator sets
Table of Contents

Advertisement

Refer
Status Event
to
or Fault
Menu
Starter 'B'
10
Starting Aid
(see Time Delay
Starting Aid)
Sync TImeout
10, 16
System Ready
10
Time Delay Engine
8, 10
Cooldown (TDEC)
Time Delay Engine
8, 10
Start (TDES)
Time Delay Starting
8, 10
Aid
Underfrequency
7, 10
Undervoltage
7, 8,
Shutdown
10
Weak Battery
10
* DD/MTU engine with MDEC/ADEC
[ NFPA applications
User-Defined Settings
Calibration
Voltage Adjustment
Underfrequency Unload
Frequency Setpoint
Underfrequency Unload
Slope
Reactive Droop
Regulator gain or stability
Volts match window
Volts match gain
Volts match reset
Synch frequency window
Frequency match gain
PGEN ID
No. of PGEN nodes
Phase match window
Phase match gain
Phase match reset
Dwell time
First on close time delay
Fail to switch time delay
Volt/frequency ok timer
TP-6356 4/12
Relay
Driver
Output
(RDO)
Digital Display
STARTER 'B'
FAILURE
SYNC
TIMEOUT
RDO-1
(lead 60)
DELAY ENG
RDO-4
COOLDOWN
(lead 70C)
DELAY ENG
RDO-15
START
RDO-16
UNDER
FREQUENCY
UNDER
VOLTAGE
WEAK
BATTERY
Refer
to
Menu
Digital Display
11
VOLT ADJ
11
FREQUENCY SETPOINT
11
SLOPE
11
VOLTAGE DROOP
11
REGULATOR GAIN ADJ
16
VOLTS MATCH WINDOW
16
VOLTS MATCH GAIN
16
VOLTS MATCH RESET
16
SYNCH FREQ WINDOW
16
FREQ MATCH GAIN
16
GENERATOR ID
16
NBR OF NODES ON BUS
16
PHASE MATCH WINDOW
16
PHASE MATCH GAIN
16
PHASE MATCH RESET
16
DWELL TIME
16
FIRST ON CLOSE TD
16
FAIL TO SYNCH TD
16
VOLT_FREQ OK TIMER
Default
Selection
Range Setting
60 sec.
delay
00:00--10:00
5:00
min:sec
00:00--5:00
00:00
min:sec
0--10 sec.
0:00
80%--100%
97% FAA
80%
70%--100%
70%
30-sec time
delay
Fixed
60% of
nominal
] 3x (times) energize time shown in Menu 17
Range Setting
±20% of system voltage
40 to 70 Hz
0--10% of rated voltage
volts per cycle
0--10% of system voltage
1--10000
+/-- 1--10% V
0--99.99
0--50 sec.
+/-- 0.1--5 Hz
0.01--99.99
0--8 (0 by reset)
0--8 (0 by reset)
+/-- 1.0--20.0 degrees
0--99.99
0--50 sec.
0.1--30 sec.
0.5--10 sec.
10--600 sec.
0--10 sec.
Section 7 Decision-Makerr 6000 Controller
Inhibit
Time
Time
Delay
User-Defined
Delay
(sec.)
(sec.)
Not adjustable
0--600
Not adjustable
10
5--30
2
User-Defined
Default Selection
System voltage
1 Hz below system freq.
(ECM)
2 Hz below system freq.
(non-ECM)
3.1% of system
voltage
4% of system voltage
100
+/-- 1.0% V
1.00
1.0 sec.
+/-- 2.0 Hz
1.00
0
0
+/-- 5.0 degrees
1.0
1.0 sec.
0.3 sec.
0.5 sec.
300 sec.
0.5 sec.
Settings
Settings
121

Hide quick links: