2. Acquire display data from the old controller for
entry in the new controller.
Certain data cannot be stored on electronic media
for archival purposes and must be entered using a
PC or the controller keypad.
When possible, make note of the following data
from the old controller for entry in the new
controller. If the old controller is not functional, the
installer must determine and document this
information for entry later in this procedure. See
Section 7.6.3 for the Controller User-Defined
Settings form.
a. From Menu 4, Operational Records
D
Total Run Time Hours
D
Total Run Time Loaded Hours
D
Total Run Time Unloaded Hours
b. From Menu 7, Generator System
D
Metric Units, yes or no
c. From Menu 13, Communication
D
Protocol Modbus 0
D
Modbus online, yes or no
D
Connection type
d
Single, yes or no
d
Convertor, yes or no
D
Primary port
d
RS-485
d
RS-232
D
Address
D
BAUD rate
d
9600
d
19200
D
Protocol Modbus 1
D
Modbus online, yes or no
D
Connection type
d
Single, yes or no
d
Convertor, yes or no
D
Primary port
d
RS-485
d
RS-232
D
Address
D
BAUD rate
d
9600
d
19200
TP-6356 4/12
D
Protocol Dial Out (if the option is installed)
D
Enable, yes or no
D
Target
d
Pager
d
Modem
D
Phone number
D
Phone delay
D
Pin number
D
Pin delay
d. From Menu 20, Factory Setup
D
Final assembly date
D
Final assembly clock number
D
Model number
D
Spec number
D
Serial number
3. Acquire display data from the old controller for
reference purposes.
When possible, write down the old controller
display data in Section 7.6.3, User-Defined
Settings. This data is not required for the new
controller but may be needed for future reference.
If the old controller is not functional, the information
is no longer retrievable.
4. Remove the generator set from service.
a. Press the generator set controller OFF button.
b. Disconnect the power to the battery charger, if
equipped.
c. Disconnect the generator set engine starting
battery(ies), negative (--) lead first.
Section 7 Decision-Makerr 6000 Controller
109