1. AC fuse terminal block
Figure 3-20 AC Fuse Terminal Block
Overcrank Lamp
Engine starts and runs, but overcrank lamp flashes.
Note: The overcrank lamp will flash if speed sensor
signal is absent longer than one second.
Excessive speed sensor air gap?
Open speed sensor circuit? Check continuity of wire 2
(black), wire 16 (white), and wire 24 (red) between P1
connector and speed sensor. Check for 10-12 volts DC
across speed sensor (+) positive terminal and (--)
negative terminals. Check wire 16 for 3--6 volts DC,
and wire 24 for 8--10 volts DC while unit is
cranking/running. Does test check out okay?
Repair circuit.
54
Section 3 Decision-Makerr 3+ Troubleshooting
TP-5353-6
No
No
1
2
1. (+) Connection—P4-6
2. (--) Connection—P4-1
Figure 3-21 Checking Input Voltage to
Lamp Circuit Board
Adjust speed sensor air gap to
Yes
specifications. See Section 1.
Is speed sensor
defective? See
Yes
speed sensor test in
Section 8.20.
No
Replace main
control board.
3-187
Replace speed
Yes
sensor.
TP-6356 4/12