10. Install the program/data files.
a. Connect the PC to the controller at P19
(RS-485). See Figure 7-8.
b. Insert the personality profile backup disk/drive
and load the data.
Software and TP-6701 SiteTecht Software
Operation Manual for details.
c. Use the controller keypad to go to Menu 20,
Factory Setup. See Figure 7-9 for displays.
1
2
6
1. P19—RS-485 port (Modbusr to DPS, SiteTecht software,
Ethernet converter)
2. P21—PGEN paralleling connection, RS-485 port
3. P18—Modbusr, RS-232 port (Monitor III connection)
4. P20—Modbus, RS-485 port (Modbusr to remote serial
annunciator [RSA] or Ethernet converter)
5. P22—ECM (CAN) connector
6. Main logic circuit board
Figure 7-8 Main Logic Circuit Board Communication
Ports (Top View of Circuit Board)
Section 7 Decision-Makerr 6000 Controller
112
Refer to Tech Tools—
3
4
5
ADV-6533-A
MENU 20
FACTORY SETUP
FINAL ASSEMBLY DATE
DD/MM/YY
FINAL ASSEMBLY
CLOCK NO ?
OPERATING DAYS
MODEL NO
SPEC NO
GENSET SERIAL NO
ALTERNATOR PART NO
ENGINE PART NO
TEMP SENSOR
GM#####
Y/N
DISABLE LOW COOLANT
TEMP WARNING
Y/N
TEST OVERSPEED
SHUTDOWN
Y/N
SERIAL NO
CONTROLLER SERIAL NO
CODE VERSION
#.#
COPYRIGHT
####
REGULATOR
PARAMETERS
SETUP LOCK
YES
Figure 7-9 Menu 20, Factory Setup
ENTER CODE
(UNLOCKS SETUP)
#
#
#
#
#
#
(right arrow scroll thru available
sensors) (non-ECM models only)
(DD/MTU models with MDEC
only)
(DD/MTU models with MDEC
only)
#
INITIALIZE BLOCK?
Y/N
(data block failure code)
INITIALIZE EEPROM? Y/N
TP-6356 4/12
?