Kohler Decision-Maker 1 Manual page 87

Industrial generator sets
Table of Contents

Advertisement

Refer
Status Event
to
or Fault
Menu
Digital Aux. Input
9, 10
D09 Low Fuel
Pressure Shutdown
(125RZG only)
Digital Aux. Input D11
9, 10
Air/Fuel Module
(AFM) Shutdown ]
Digital Aux. Input
9, 10
D12 Detonation
Warning ]
Digital Aux. Input
9, 10
D13 Detonation
Sensing Module
(DSM) Shutdown ]
Digital Aux. Input
9, 10
D13 Knock Detection
Module (KDM)
Shutdown ]
Digital Aux. Input D14
9, 10
Low Coolant Level,
(with LCL switch) **
Digital Aux. Input
9, 10
D15 Remote
Shutdown
Digital Aux. Input
9, 10
D16 Remote Reset
Digital Aux. Input
9, 10
D17 VAR/PF mode
Digital Aux. Input
9, 10
D18 Voltage Lower
Digital Aux. Input
9, 10
D19 Voltage Raise
Digital Aux. Input
9, 10
D20 Air Damper
Indicator (if used) **
Digital Aux. Input
9, 10
D21 Idle (speed)
Mode Function
ECM Red Alarm
10
(was MDEC Yellow
Alarm) [[
ECM Yellow Alarm
10
(was MDEC Yellow
Alarm) [[
EEPROM Write
10
Failure
Emergency Stop
10
Shutdown
Engine Cooldown
(see Time Delay--)
Engine Derate Active
10
(Engine) J1939 CAN
10
Engine Shutdown
Engine Stalled
10
Engine Start
(see Time Delay--)
* All models, except Waukesha-powered models.
[ Non-paralleling applications
] Waukesha-powered models
w Paralleling applications
TP-6356 4/12
Relay
Driver
Output
(RDO)
Digital Display
D09
LOW FUEL
SHUTDOWN
D11
AFM
SHUTDOWN
D12
DETON
WARNING
D13
DETON
SHUTDOWN
D13
KNOCK
SHUTDOWN
D14 LOW
RDO-19
COOLANT LVL
D15 REMOTE
SHUTDOWN
D20
RDO-23 *
AIR DAMPER
(lead 56)
D21
RDO-21
IDLE MODE
ACTIVE
ECM RED ALARM
ECM YELLOW
ALARM
EEPROM WRITE
FAILURE
EMERGENCY
RDO-14
STOP
(lead 48)
ENGINE DERATE
ACTIVE
J1939 CAN
SHUTDOWN
ENGINE
STALLED
Default
Selection
Range Setting
Fixed
5 sec.
inhibit,
0 sec. delay
Fixed
0 sec.
inhibit,
0 sec. delay
Fixed
2 sec.
inhibit,
0 sec. delay
Fixed
0 sec.
inhibit,
0 sec. delay
Fixed
0 sec.
inhibit,
0 sec. delay
Fixed
30 sec.
inhibit,
5 sec. delay
0 sec.
inhibit,
0 sec. delay
Fixed
0 sec.
inhibit,
0 sec. delay
Fixed inhibit time
0 sec.
inhibit,
60 sec.
delay
** NFPA applications
[[ DDC/MTU engine with MDEC/ADEC
]] FAA only
Section 5 Decision-Makerr 550 Controller
Inhibit
Time
Time
Delay
User-Defined
Delay
Settings
(sec.)
(sec.)
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Not adjustable
0--600
Not adjustable
or 9:99
for
infinity
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Not adjustable
87