b. Use the controller keypad to go to Menu 6, Time
and Date.
Use the information from the
controller operation manual as necessary to set
the time and date.
19. Perform the Menu 7, Generator System, entries for
English or metric displays.
a. Press the RESET MENU key on the controller
keypad.
b. Use the controller keypad to go to Menu 7,
Generator System. Use the information from
the controller operation manual as necessary
to change metric unit, yes or no.
20. Perform the Menu 12, Calibration, entries.
a. See the controller operation manual for
disconnecting
Disconnect ribbon connector P2 prior to
zeroing out (resetting) the auxiliary analog
inputs.
b. Press the RESET MENU key on the controller
keypad.
c. Use the controller keypad to go to Menu 12,
Calibration.
Use the information from the
controller operation manual as necessary to
scale AC analog inputs.
d. With the information previously recorded from
step 2, scale the auxiliary analog inputs. Use
the information from the controller operation
manual as necessary.
21. Add the user parameters.
a. Choose one of the following methods to load
the user parameters.
D
Backup disk/drive. Use a PC with SiteTecht
software to load the data from the user
parameter backup disk/drive. Enable Menu
14, Programming Mode—Remote.
D
Paper form. Use a PC to enter the user
parameter
Decision-Makerr 6000 Controller Operation
Manual
TP-6750,
Defined Settings form, the User-Defined
form located in Section 7.6.3, or other similar
form.
Enable Menu 14, Programming
Mode—Remote. Use a PC with SiteTecht
software to load the data.
D
Controller menu. Use the controller keypad
to manually enter the user parameter data
from the filled-out Decision-Makerr 6000
TP-6356 4/12
the
ribbon
connector.
data
from
the
filled-out
Appendix B,
Controller
Appendix B, User- Defined Settings form,
the User-Defined form located in Section
7.6.3, or other similar form. Enable Menu 14,
Programming Mode—Local.
information from the controller operation
manual as necessary.
b. Create a new user parameter data backup
disk/drive if any changes are made. Use a PC
with SiteTecht software to save the data.
c. Disconnect the PC at P19 (RS-485).
d. Install the P18 (RS-232) remote communication
connection, as necessary.
e. Swing the front controller panel up and replace
and tighten the screws, as necessary.
Note: If the controller is panel mounted to the
f. Replace the controller cover and hardware.
Tighten all controller screws.
22. Restore the generator set to service.
a. Perform the Menu 13, Communication, entries.
D
Press the RESET MENU key on controller
keypad.
D
Use the controller keypad to go to Menu 13,
Communications.
D
With the information previously recorded
from step c., complete the communication
entries as necessary for the application. Use
the information from the controller operation
manual as necessary.
b. Perform the Menu 14, Programming Mode
entries.
D
Press the RESET MENU key on controller
keypad.
D
Use the controller keypad to go to Menu 14,
Programming Mode.
User-
D
Change the entries for the application as
necessary.
c. The generator set system is now ready to
function.
d. Press the generator set controller AUTO button
for startup by remote transfer switch or remote
start/stop switch.
Operation
Manual TP-6750,
junction box, replace the access panel
and respective hardware.
Section 7 Decision-Makerr 6000 Controller