10. Stop the generator set.
a. Place the generator set master switch in the
OFF position.
b. Disconnect the generator set engine starting
battery(ies), negative (--) lead first.
11. Remove the oxygen sensor and interface harness.
a. Allow the generator set exhaust system to cool.
b. Disconnect the battery clips from the battery.
c. Disconnect the interface harness from the
digital voltmeter (DVM).
d. Disconnect the interface harness from the
oxygen sensor.
e. Remove the oxygen sensor from the exhaust
tube.
TP-6356 4/12
f. Apply a small amount of antiseize compound to
the pipe plug and reinstall the pipe plug into the
exhaust tube.
g. Remove the manometer hose fitting from the
solenoid fuel valve.
h. Apply a small amount of antiseize compound to
the pipe plug and reinstall the pipe plug into the
solenoid fuel valve.
12. Restore the generator set to service.
a. Check that the generator set master switch is in
the OFF position.
b. Reconnect the generator set engine starting
battery, negative (--) lead last.
c. Reconnect the power to the battery charger, if
equipped.
Section 9 Gas Fuel Systems
187