Kohler Decision-Maker 1 Manual page 118

Industrial generator sets
Table of Contents

Advertisement

Refer
Status Event
to
or Fault
Menu
Enable Synch D06
9, 10,
16
Engine Cooldown
(see Time Delay--)
Engine Stalled
10
Engine Start
(see Time Delay--)
EPS (Emergency
10
Power System)
Supplying Load
External Breaker Trip
10
Extra PGEN Node
10, 16
Field Overvoltage
9, 10
D04
(M4, M5, M7, or M10
alternator only)
First On Fault
9, 16
Generator Set
7
Parameter Warning
Generator Set
10
Running
Generator Set Serial
20
Number Warning
Ground Fault
9, 10
Detected (Digital
Input)
High Battery Voltage
10
High Coolant
10
Temperature
Shutdown
High Coolant
10
Temperature Warning
High Oil Temperature
9, 10
Shutdown
High Oil Temperature
9, 10
Warning *
Idle (speed) Mode
9, 10
Function D21
In Synch (Dwell
10
Time)
Intake Air
10
Temperature
Shutdown *
Intake Air
10
Temperature
Warning *
Internal Fault
10
Shutdown
J1939 CAN
10
Shutdown
Key Switch Locked
10
* DD/MTU engine with MDEC/ADEC
[ NFPA applications
Section 7 Decision-Makerr 6000 Controller
118
Relay
Driver
Output
(RDO)
Digital Display
ENGINE
STALLED
EPS
RDO-18
SUPPLYING
LOAD
EXTRNL
RDO-31
BREAKER
TRIP
EXTRA PGEN
NODE
FIELD
OVERVOLTAGE
D04
FIRST ON
FAULT
GENSET
PARAM
WARNING
RDO-22
(lead 70R)
GENSET S/N
WARNING
GROUND
RDO-17
FAULT
HIGH
BATTERY
VOLTAGE
HI COOL TEMP
(lead 36)
SHUTDOWN
HI COOL TEMP
RDO-6
WARNING
(lead 40)
HI OIL TEMP
SHUTDOWN
HI OIL TEMP
WARNING
IN SYNCH
RDO-27
INTAKE AIR
TEMP SDWN
INTAKE AIR
TEMP WARN
INTERNAL
FAULT
J1939 CAN
SHUTDOWN
KEY SWITCH
RDO-21
LOCKED
Default
Selection
Range Setting
Fixed
0 sec.
inhibit,
0 sec. delay
Fixed
1% of rated
line current
Fixed
Fixed
1 sec.
inhibit,
15 sec.
delay
0.5 sec.
delay
14.5--16.5 V (12 V)
16 V (12 V)
29--33 V (24 V)
32 V (24 V)
Fixed
Fixed
Fixed
Fixed
Fixed inhibit time
0 sec.
0--600 sec. delay or
inhibit,
9.99 (infinite)
60 sec.
delay
0.3 sec.
Fixed
Fixed
] 3x (times) energize time shown in Menu 17
Inhibit
Time
Time
Delay
User-Defined
Delay
Settings
(sec.)
(sec.)
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Not adjustable
0.5--
10
Not adjustable
Not adjustable
Not adjustable
Not adjustable
10
30
5
Not adjustable
30
0
Not adjustable
30
5
Not adjustable
30
0
Not adjustable
0
0--600
0.1--
30
30
0
Not adjustable
30
5
Not adjustable
Not adjustable
Not adjustable
Not adjustable
TP-6356 4/12