Kohler Decision-Maker 1 Manual page 71

Industrial generator sets
Table of Contents

Advertisement

D
Fixed Voltage when entry is beyond the range of
limited entries for the respective alternator. Occurs
when the alternator is not rated for the value entered.
Updated parameter files may be available by
contacting an authorized service dealer/distributor.
Func (Function) Used by (RDO) XX Reassign?
appears when the user attempts to assign an RDO to a
function already assigned.
Internal Error appears when controller logic detects a
functional sequence error.
Invalid Code appears when the user attempts to enter:
D
An invalid access code for programming mode setup,
or
D
An invalid access code for setup unlock.
Invalid Menu ID appears when the user attempts to
enter a menu number which is unavailable or
non-functional.
N/A appears when data to be displayed is not available.
No Input Assigned appears when the user attempts to
assign any of the following system faults to an RDO
where the digital input is not defined. See digital input
scale requirements in Menu 12—Calibration.
D
Air damper indicator
D
Battery charger fault
D
Ground fault
D
High oil temperature shutdown
D
Low coolant level
D
Low fuel
TP-6356 4/12
Not in Local Program Mode appears when the user
attempts to program using the keypad when the
programming mode is set for remote or off.
Not User Selectable appears when the user attempts
to change an analog or digital input that is factory-
reserved. Items identified as not user selectable are
included for specific applications.
SHUTDOWN is enabled with a Waukesha-powered
model.) The user cannot disable an analog or digital
input when identified as not user selectable.
Figure 5-2 in User Inputs for factory-reserved digital
and analog inputs which are not user selectable.
Output in Use appears when the user attempts to
modify or reassign an active RDO.
Port in Use appears when the user attempts to use an
already assigned communications port.
Range Error appears when the user attempts to enter:
D
A numeric input that is not within the acceptable
range of the system settings, time delays, addresses,
etc.
D
An invalid analog or digital input number.
D
An invalid date/time.
Remove Load appears when trying to calibrate the
voltage regulator in menu 12 with load connection. The
voltage regulation calibration must be performed during
a no load condition.
Setpoint Values Cannot be Equal appears when the
user attempts to enter the same value for both setpoints
during the analog input calibration.
Section 5 Decision-Makerr 550 Controller
(Example:
AFM
See
71