Kohler Decision-Maker 1 Manual page 180

Industrial generator sets
Table of Contents

Advertisement

Model,
LP, 60 Hz
kW
Engine
3.0 L
1--3
30
4.3 L
35
4.3 L
45
1--3, 2--5
5.0 L
50
5.7 L
60
5.7 L
80
100
8.1 L
1--5
125
Figure 9-36 Fuel and Frequency Jumper Connections on TB12
30- -60 kW models.
a.
D
Remove the right side panel of the junction
box and locate the fuel configuration terminal
strip TB12.
D
30 kW model with 3.0 L engine only.
Attach a user-supplied 18 ga. jumper wire
between terminals 1 and 3 (LP gas vapor
fuel). See Figure 9-37 for frequency jumper
wire requirements.
Note: No jumper wire is used with natural
gas fuel.
30 kW model with 4.3 L engine and
35- -60 kW models. Move the jumper wire
from terminals 1 and 5 (natural gas fuel) to
terminals 1 and 3 (LP gas vapor fuel). See
Figure 9-38 for frequency jumper wire
requirements.
D
Attach the junction box right side panel.
1
1. Junction box (rear view)
2. Fuel configuration terminal strip TB12
3. Jumper wire between terminals 1 and 3
(LP gas vapor fuel)
4. Frequency jumper wire
(60 Hz: none; 50 Hz: terminals 2 and 3)
Figure 9-37 Fuel Configuration Jumper Wire
(LP Fuel, 60 Hz, 30 kW [3.0 L] Model)
180 Section 9 Gas Fuel Systems
Straight Gas Fuel
LP, 50 Hz
NG, 60 Hz
1--3, 2--3
none
1--3, 2--3
1--5, 2--5
1--5, 2--5
none
3
2
GM21300/GM21218
NG/LP Dual Fuel
NG, 50 Hz
60 Hz
2--3
none
1--5, 2--3
1--5, 2--5
2--5
none
1. Junction box (rear view)
2. Fuel configuration terminal strip TB12
3. Jumper wire between terminals 1 and 3
(LP gas vapor fuel)
4. Frequency jumper wire
(60 Hz: terminals 2 and 5; 50 Hz: terminals 2 and 3)
Figure 9-38 Fuel Configuration Jumper Wire
80- -125 kW models.
b.
D
Remove the right side panel of the junction
box and locate the fuel configuration terminal
strip TB12. See Figure 9-39.
4 not
used
1. Junction box (rear view)
2. Fuel configuration terminal strip TB12
3. Jumper wire between terminals 1 and 5 (LP gas vapor
fuel)
4. Frequency jumper wire
(60 Hz: no jumper; 50 Hz: terminals 2 and 5)
Figure 9-39 Fuel Configuration Jumper Wire
LP Liquid Withdrawal
50 Hz
60 Hz
2--3
1--3
1--5, 2--3
1--3, 2--5
2--5
1--5
1
2
(LP Fuel, 60 Hz, 30 kW [4.3 L] and
35--60 kW Models)
1
2
(LP Fuel, 60 Hz, 80--125 kW Models)
50 Hz
1--3, 2--3
1--3, 2--3
1--5, 2--5
3
4
GM21300/GM21218
4 not
3
used
GM21300/GM25000
TP-6356 4/12