k. Change the final assembly clock number.
D
Arrow down to the FINAL ASSEMBLY
CLOCK NO. display.
D
Enter the final assembly clock number using
the data recorded from the old controller. If
data from the old controller is not available,
keep the default setting.
D
Press the ENTER key if making a new entry.
l. Change the serial number.
service replacement kit will show the GENSET
SERIAL NO. as 123456. After the personality
profile is loaded, the GENSET SERIAL NO.
shows the correct serial number for the
respective generator set. Use the GENSET
SERIAL NO. to update the SERIAL NO. display
as follows:
D
Arrow down to the SERIAL NO. display.
D
Enter the serial number of the generator set
using data recorded from the old controller or
as shown on the generator set nameplate. If
the serial number is six digits, enter a leading
zero for a seven-digit serial number.
D
Press the ENTER key. The GENSET S/N
WARNING display no longer appears when
the GENSET SERIAL NO. and SERIAL NO.
match.
12. Perform the Menu 13, Communications entries.
a. Press the RESET MENU key on controller
keypad.
b. Use the controller keypad to go to Menu 13,
Communications.
c. Complete the communication entries as
necessary for remote programming. Use the
information from the controller operation
manual as necessary.
13. Perform the Menu 14, Programming mode entries.
a. Press the RESET MENU key on the controller
keypad.
b. Use the controller keypad to go to Menu 14,
Programming Mode, and select programming
mode—remote. Use the information from the
SiteTecht software and refer to TP-6701
SiteTecht Software Operation Manual for
details.
Section 7 Decision-Makerr 6000 Controller
114
14. Perform the Factory Setup entries seen in Menu 20
The controller
15. Perform the Menu 14, Programming mode entries.
16. Perform the Menu 4, Operational Records.
17. Lock the Menu 20, Factory Setup entries.
18. Enter the Menu 6, Time and Date, settings.
using SiteTecht. Use the information from the
SiteTecht software and refer to TP-6701
SiteTecht Software Operation Manual for details.
a. Change the model number.
D
Go to the MODEL NO. display.
D
Enter the model number using the data
recorded from the old controller or as shown
on the generator set nameplate.
b. Change the spec (specification) number.
D
Go to the SPEC NO. display.
D
Enter the spec number using the data
recorded from the old controller or as shown
on the generator set nameplate.
a. Press the RESET MENU key on the controller
keypad.
b. Use the controller keypad to go to Menu 14,
Programming Mode, and select programming
mode—local. Use the information from the
controller operation manual as necessary.
a. Press the RESET MENU key on controller
keypad.
b. Use the controller keypad to go to Menu 4,
Operational Records.
c. Complete the operational records entries as
necessary.
Use the information from the
controller operation manual as necessary.
a. Press the SETUP MENU key on the controller
keypad.
b. Use the controller keypad to go to Menu 20,
Factory Setup.
c. Arrow down to the SETUP LOCK display.
d. Press the YES key to lock the setup and
prevent alterations to Menu 20, Factory Setup.
a. Press the RESET MENU key on the controller
keypad.
TP-6356 4/12