h. Press the down arrow key to L1--L2 Volts. Use
the numeric keys to enter the user measured
value. Press the Enter key.
i. Record the voltage on the resistive load bank or
connect an RMS voltmeter to each of the
remaining voltage connections shown in
Figure 4-8. Use the numeric keys to enter the
user
measured
corresponding voltage displays.
Enter key. Press the down arrow key to access
the next display.
j. Record the amps from the resistive load bank
or connect an RMS ammeter to each of the
amperage connections shown in Figure 4-8.
Use the numeric keys to enter the user
measured value of each of the corresponding
amp displays. Press the Enter key. Press the
down arrow key to access the next display.
k. Press the down arrow key to access the
Resistive Load? display.
l. Press Yes and the Enter key.
Note: Enter only a Yes response and apply
only a purely resistive load. Failure to
comply with this request will cause
incorrect kW load and power factor
values.
m. Press the down arrow key to access the Battery
VDC display.
n. Use the numeric keys to enter the measured
engine electrical system voltage. Press the
Enter key.
o. Press the Reset Menu key.
p. Press the Enter key. The display indicates
Store Set Points. Wait until display changes to
Enter Menu 1- -14.
q. Place the controller master switch to the OFF
position to stop the generator set.
66
Section 4 Decision-Makerr 340 Controller
value
of each
of the
Press the
12. Enter the Menu 3, Time and Date, settings.
a. Press the Reset Menu key on the controller
keypad.
b. Go to Menu 3, Time and Date.
information from the controller operation
manual as necessary to set the time and date.
13. Restore the generator set to service.
a. Perform the Menu 10, Remote Control entries.
D
Press the Reset Menu key on controller
keypad.
D
Go to Menu 10, Remote Control.
D
With the information previously recorded
from step 1, complete the communication
entries as necessary for the application. Use
the information from the controller operation
manual as necessary.
b. Perform the Menu 11, Programming Mode
entries.
D
Press the Reset Menu key on controller
keypad.
D
Go to Menu 11, Programming Mode.
D
Change the entries for the application as
necessary.
c. The generator set system is now ready to
function.
d. Move the generator set master switch to AUTO
for startup by remote transfer switch or remote
start/stop switch.
Use the
TP-6356 4/12