Gsdml File; Related Drive Parameters - YASKAWA PROFINET JOHB-SMP3 Technical Manual

Hide thumbs Also See for PROFINET JOHB-SMP3:
Table of Contents

Advertisement

6 Related Drive Parameters

GSDML File

To facilitate network implementation, the GSDML file can be downloaded directly from the JOHB-SMP3 card
using a standard web interface. Refer to
You can also obtain a GSDML file from one of the following websites depending on your region:
• U.S.: http://www.yaskawa.com
• Europe: http://www.yaskawa.eu.com
• Japan: http://www.e-mechatronics.com
• Other areas: Check the back cover of these manuals.
For questions, contact Yaskawa or a Yaskawa representative.
Note:
Download the GSDML file for YASKAWA AC Drive Option JOHB-SMP3. If you download an incorrect GSDML file, this product will
not operate as an IO-Device in the network.
6
Related Drive Parameters
These parameters set the drive for operation with the option. Make sure that the parameter settings in this table are
correct before you start network communications.
Note:
• Hex.: MEMOBUS addresses that you can use to change parameters over network communication are represented in hexadecimal
numbers.
• Expert: Some monitors are available in Expert Mode only. When A1-01 = 3 [Access Level Selection = Expert Level], Expert Mode
monitors can be displayed on the keypad.
No.
Name
(Hex.)
b1-01
Frequency Reference
Selection 1
(0180)
b1-02
Run Command Selection 1
(0181)
F6-01
Communication Error
Selection
(03A2)
F6-02
Comm External Fault (EF0)
Detect
(03A3)
22
PROFINET Page on page 49
Selects the input method for frequency reference.
0 : Keypad
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option PCB
4 : Pulse Train Input
Note:
• Set b1-01 = 3 to use the IO-Controller to control the frequency reference of the drive.
• The default setting is different for different drives. Refer to the instruction manual of your
specific drive for more information.
Sets the input method for the Run command.
0 : Keypad
1 : Digital Input
2 : Memobus/Modbus Communications
3 : Option PCB
7 : AUTO Command + Term Run
8 : AUTO Command + Serial Run
9 : AUTO Command + Option Run
Note:
• Set b1-02 = 3 or 9 to start and stop the drive with the IO-Controller using serial
communications.
• The setting range is different for different drives. Refer to the instruction manual of your
specific drive for more information.
Selects drive response when the drive detects a bUS [Option Communication Error] error during
communications with the option.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Alarm (Run at d1-04)
5 : Alarm - Ramp Stop
Note:
• When you set this parameter to 3 or 4, the drive will continue operation after it detects a
fault. Separately prepare safety protection equipment and systems, for example fast-stop
switches.
• Refer to the drive manual to know if settings 4 and 5 are available.
• The setting range for 1000-Series drives is different for different software versions. Refer to
the Peripheral Devices & Options section of the drive instruction manual for more
information.
• Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
Selects the conditions at which EF0 [Option Card External Fault] is detected.
0 : Always Detected
for more information.
Description
YASKAWA SIEP C730600 0KA PROFINET Technical Manual
Default
(Range)
1
(0 - 4)
1
(0 - 9)
1
(0 - 5)
0
(0, 1)