YASKAWA PROFINET JOHB-SMP3 Technical Manual page 43

Hide thumbs Also See for PROFINET JOHB-SMP3:
Table of Contents

Advertisement

Positive Read Response to Read Request
Negative Response to Yaskawa P-Drive Read Request
Yaskawa P-Drive Profile-Specific Parameters
Yaskawa P-Drive parameters contain data of the drive in standard form. The table below describes the supported
Yaskawa P-Drive parameters.
Parameter
Read/Write
922
Read
944
Read
947
Read
964
Read
965
Read
967
Read
968
Read
977
Read/Write
61000
Read
61001
Read
61002
Read
61003
Read
61004
Read
Fault Buffer Mechanism
Yaskawa P-Drive profile has a mechanism that can store five fault situations to Yaskawa P-Drive parameters.
Fault and diagnostic data, like fault number and fault code can be accessed simultaneously with only one
subindex. The mechanism consists of two Yaskawa P-Drive parameters:
YASKAWA SIEP C730600 0KA PROFINET Technical Manual
Data type
Unsigned16
Telegram selection
Unsigned16
Fault message counter
Fault number. (coded according to DRIVECOM profile) Refer to parameter 945 for information about Subindex
Array [5] Unsigned16
Contents.
Device identification Subindex Contents
0: Manufacturer
1: Device type
Array [6] Unsigned16
2: Version
3: Firmware date (year)
4: Firmware date (day/month)
5: Number of Drive Objects (DO)
Profile number of this device.
Octet String2
0328h = Profile 3, Version 40
Unsigned16
Control word (CW)
Unsigned16
Status word (SW)
Stores parameters to non-volatile memory Value Description
0: No action
Unsigned16
1: Stores parameters
Note:
The parameter must do a zero-to-one transition and the motor must be stopped.
VisibleString24
Name of station
Unsigned32
IP of station
Array [6] Unsigned8
MAC of station
Unsigned32
Default gateway of station
Unsigned32
Subnet mask of station
8 Communication
Description
43

Advertisement

Table of Contents
loading

Table of Contents