YASKAWA PROFINET JOHB-SMP3 Technical Manual page 25

Hide thumbs Also See for PROFINET JOHB-SMP3:
Table of Contents

Advertisement

No.
Name
(Hex.)
F7-14
Duplex Mode Selection
(03F2)
F7-15
Communication Speed
Selection
(03F3)
F7-16
Timeout Value
(03F4)
F7-23 - F7-27
Dynamic Out Param 1 to 10
for CommCard
(03FB - 03FF)
F7-28 - F7-32
(0370 - 0374)
F7-33 - F7-42
Dynamic In Param 1 to 10
for ComCard
(0375 to 037E)
H5-11
Communications ENTER
Function Selection
(043C)
(Function common to
communication option)
o1-03
Frequency Display Unit
Selection
(0502)
YASKAWA SIEP C730600 0KA PROFINET Technical Manual
Note:
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
• The PLC will assign the IP addresses when F7-13 = 1 or 2.
Sets duplex mode settings (Port 1 (CN1A)/Port 2 (CN1B)). Set this parameter to 1 or 2 for
PROFINET. Set F7-15 = 100 [Communication Speed Selection = 100/100 Mbps (100 Mbps/100
Mbps] if you set this parameter to 2.
0 : Half/Half (Half Duplex/Half Duplex)
1 : Auto/Auto (Auto Negotiation/Auto Negotiation)
2 : Full/Full (Full Duplex/Full Duplex)
3 : Half/Auto (Half Duplex/Auto Negotiation)
4 : Half/Full (Half Duplex/Full Duplex)
5 : Auto/Half (Auto Negotiation/Half Duplex)
6 : Auto/Full (Auto Negotiation/Full Duplex)
7 : Full/Half (Full Duplex/Half Duplex)
8 : Full/Auto (Full Duplex/Auto Negotiation)
Note:
You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the communications speed (Port 1 (CN1A)/Port 2 (CN1B)). Set this parameter to 100 for
PROFINET.
10 : 10/10 Mbps (10 Mbps/10 Mbps)
100 : 100/100 Mbps (100 Mbps/100 Mbps)
101 : [Not Used/No function] 10/100 Mbps (10 Mbps/100 Mbps)
102 : [Not Used/No function] 100/10 Mbps (100 Mbps/10 Mbps)
Note:
• F7-15 is only effective when the port is set to half or full duplex in F7-14 [Duplex Mode
Selection].
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the bUS fault delay time to the drive after the option detects a bUS fault to let the network
condition self-correct.
Note:
• This parameter is not available in all 1000-series drives.
• Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
Sets configurable outputs 1 to 10 that are used in some of the PROFINET I/O modules. Each
parameter contains a MEMOBUS/Modbus address. The values received from the PLC for the
configurable outputs will be written to this corresponding MEMOBUS / Modbus addresses. A
MEMOBUS/Modbus address value of 0 means that the value received from the PLC for the
configurable outputs will not be written to any MEMOBUS/Modbus register.
Sets configurable inputs 1 to 10 which are used in some of the PROFINET I/O modules. Each
parameter contains a MEMOBUS/Modbus address. The values sent to the PLC via the
configurable inputs will be read from the corresponding MEMOBUS/Modbus addresses. A
MEMOBUS/Modbus address value of 0 means that the value sent for the configurable inputs is
not defined by the user, therefore the option default register value will be returned.
Sets when an Enter command is necessary to use MEMOBUS/Modbus communications to change
parameter values.
0 : Parameter changes are activated when ENTER command is written
1 : Parameter changes are activated immediately. No ENTER command is necessary.
Sets the display units for the frequency reference and output frequency. Changes to this parameter
take effect immediately. It is not necessary to cycle power on the drive.
0 : 0.01Hz units
1 : 0.01% units
2 : min
-1
(r/min) unit
3 : User Units (o1-09 -o1-11)
Description
6 Related Drive Parameters
Default
(Range)
1
(0 - 8)
10
(10 - 102)
0.0 s
(0.0 s - 30.0 s)
0
(-)
0
(-)
0
(0, 1)
0
(0 - 3)
25