Remote Setpoint Via A 0/4 - ProMinent DULCOMETER Assembly And Operating Instructions Manual

Multi-parameter controller
Table of Contents

Advertisement

Setting the [Control]
Multiplicative disturbance variable
With the multiplicative disturbance variable, the disturbance variable of the setpoint con‐
troller can be influenced over the entire control range. Here a proportionality factor of
0.00 = 0% and 1.00 = 100 %, including all intermediate values.
Disturbance variable
Parameter Default set‐
ting
Function
Off
Signal
Frequency
source
DI 2
Effect
additive
Nominal
10 Hz
value
10.11
Remote setpoint via a 0/4 ... 20 mA analog signal
Continuous display ➨
[Remote setpoint (mA)] ➨
Availability of the remote setpoint
The menu [Remote setpoint (mA)] is only available with the 1-channel control of the
controller.
110
Possible
Minimum
values
value
On/Off
Frequency
DI 2 / mA
input 2
Additive /
multiplica‐
tive
1...500 Hz
1 Hz
[Control] ➨
or
[Remote setpoint]
Maximum
Remark
value
Switches the dis‐
turbance variable
function on or off
Specifies the
signal source from
which the interfer‐
ence signal origi‐
nates
Specifies the
effect of the dis‐
turbance variable
500 Hz
Specifies the max‐
imum frequency of
the contact water
meter at maximum
flow
[Control] ➨