Appendix A Specifications|
Voltage Class
Model Number VFD-XXXE
Max. Applicable Motor Output (kW)
Max. Applicable Motor Output (hp)
Rated Output Capacity (kVA)
Rated Output Current (A)
Maximum Output Voltage (V)
Output Frequency (Hz)
Carrier Frequency (kHz)
Rated Input Current (A)
Rated Voltage/Frequency
Voltage Tolerance
Frequency Tolerance
Cooling Method
Weight (kg)
Control System
Frequency Setting Resolution
Output Frequency Resolution
Torque Characteristics
Overload Endurance
Skip Frequency
Accel/Decel Time
Stall Prevention Level
DC Brake
Regenerated Brake Torque
V/f Pattern
Frequency
Setting
External Signal
Operation
Setting
External Signal
Signal
Multi-function Input Signal
A-2
004
0.4
0.5
1.2
1.5
1.9
Natural Cooling
1.2

General Specifications

SPWM(Sinusoidal Pulse Width Modulation) control (V/f or sensorless vector
Including the auto-torque/auto-slip compensation; starting torque can be
0.1 to 600 seconds (2 Independent settings for Accel/Decel time)
Operation frequency 0.1-600.0Hz, output 0-100% rated current
Approx. 20% (up to 125% possible with optional brake resistor or externally
mounted brake unit, 1-15hp (0.75-11kW) models have brake chopper built-in)
Keypad
Potentiometer-5kΩ/0.5W, 0 to +10VDC, 4 to 20mA, RS-485 interface; Multi-
function Inputs 3 to 9 (15 steps, Jog, up/down)
Keypad
2 wires/3 wires (MI1, MI2, MI3), JOG operation, RS-485 serial interface
(MODBUS), programmable logic controller
Multi-step selection 0 to 15, Jog, accel/decel inhibit, 2 accel/decel switches,
counter, external Base Block, ACI/AVI selections, driver reset, UP/DOWN
key settings, NPN/PNP input selection
460V Class
007
015
022
0.75
1.5
2.2
1.0
2.0
3.0
2.0
3.3
4.4
2.5
4.2
5.5
3-Phase Proportional to Input Voltage
0.1~600 Hz
3-phase
3.2
4.3
7.1
3-phase, 380-480V, 50/60Hz
±
10%(342~528V)
±
5%(47~63Hz)
1.2
1.2
1.9
control)
0.01Hz
0.01Hz
150% at 3.0Hz
150% of rated current for 1 minute
Three zones, setting range 0.1-600Hz
Setting 20 to 250% of rated current
Start time 0-60 seconds, stop time 0-60 seconds
4-point adjustable V/f pattern
Setting by
Set by RUN and STOP
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
037
055
3.7
5.5
5.0
7.5
6.8
9.9
8.2
13
1-15
11.2
14
Fan Cooling
1.9
4.2
075
110
7.5
11
10
15
13.7
18.3
18
24
19
26
4.2
4.2