Multi-Function Input Terminal - Delta Electronics AC Motor Drive VFD-E User Manual

Vfd-e high performance/flexible options/micro type ac motor drives
Table of Contents

Advertisement

04.04
2
3-wire
04.05
Multi-function Input Terminal (MI3)
04.06
Multi-function Input Terminal (MI4)
04.07
Multi-function Input Terminal (MI5)
04.08
Multi-function Input Terminal (MI6)
Settings
Function
0
No Function
Multi-Step Speed
1
Command 1
Multi-Step Speed
2
Command 2
Multi-Step Speed
3
Command 3
Multi-Step Speed
4
Command 4
5
External Reset
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
External Terminal
STOP
REV/FWD
Description
Any unused terminals should be programmed to 0 to insure they
have no effect on operation.
These four inputs select the multi-speed defined by Pr.05.00 to
Pr.05.14 as shown in the diagram at the end of this table.
NOTE: Pr.05.00 to Pr.05.14 can also be used to control output
speed by programming the AC motor drive's internal PLC
function. There are 17 step speed frequencies (including
Master Frequency and Jog Frequency) to select for
application.
The External Reset has the same function as the Reset key on
the Digital keypad. After faults such as O.H., O.C. and O.V. are
cleared this input can be used to reset the drive.
Chapter 4 Parameters|
RUN
MI1 ("CLOSE":RUN)
:
MI3:("OPEN":STOP)
MI2:("OPEN": FWD)
("CLOSE": REV)
DCM
VFD-E
Factory Setting: 1
Factory Setting: 2
Factory Setting: 3
Factory Setting: 4
4-75