Ao2Terminal Analog Signal Mode; Ao2 Analog Output Signal; Ao2 Analog Output Gain - Delta Electronics AC Motor Drive VFD-E User Manual

Vfd-e high performance/flexible options/micro type ac motor drives
Table of Contents

Advertisement

Chapter 4 Parameters|
NOTE
If the scale of the voltmeter is less than 10V, refer to following formula to set Pr.12.22:
Pr.12.22 = [(full scale voltage)/10]*100%.
Example: When using voltmeter with full scale (5V), Pr.12.22 should be set to 5/10*100%=50%. If
Pr.12.21 is set to 0, the output voltage will correspond to the max. output frequency.

AO2Terminal Analog Signal Mode

12.23
Settings
Besides parameter setting, the voltage/current mode should be used with the switch.

AO2 Analog Output Signal

12.24
Settings
12.25

AO2 Analog Output Gain

Settings
Setting method for the AO2 is the same as the AO1.
4-148
0
AVO2
1
ACO2 (analog current 0.0 to 20.0mA)
2
ACO2 (analog current 4.0 to 20.0mA)
AVI3
AVI4
ACI2
ACI3
0
Analog Frequency
1
Analog Current (0 to 250% rated current)
1 to 200%
AVO1
AVO2
ACO1
ACO2
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
Factory Setting: 0
Factory Setting: 0
Unit: 1
Factory Setting: 100