Delta Electronics AC Motor Drive VFD-E User Manual page 195

Vfd-e high performance/flexible options/micro type ac motor drives
Table of Contents

Advertisement

Chapter 4 Parameters|
Settings
Function
Operation
Command
18
Selection (Pr.02.01
setting/external
terminals)
Operation
Command
19
Selection (Pr 02.01
setting/Digital
Keypad)
Operation
Command
20
Selection (Pr 02.01
setting/
Communication)
21
Forward/Reverse
Source of second
22
frequency
command enabled
Run/Stop PLC
23
Program
4-142
Description
ON: Operation command via Ext. Terminals
OFF: Operation command via Pr.02.01 setting
Pr.02.01 is disabled if this parameter value 18 is set. See the
explanation below this table.
ON: Operation command via Digital Keypad
OFF: Operation command via Pr.02.01 setting
Pr.02.01 is disabled if this parameter value 19 is set. See the
explanation below this table.
ON: Operation command via Communication
OFF: Operation command via Pr.02.01 setting
Pr.02.01 is disabled if this parameter value 20 is set. See the
explanation below this table.
This function has top priority to set the direction for running (If
"Pr.02.04=0")
Used to select the first/second frequency command source. Refer
to Pr.02.00 and 02.09.
ON: 2nd Frequency command source
OFF: 1st Frequency command source
ON: Run PLC Program
OFF: Stop PLC Program
When AC motor drive is in STOP mode and this function is
enabled, it will display PLC1 in the PLC page and execute PLC
program. When this function is disabled, it will display PLC0 in the
PLC page and stop executing PLC program. The motor will be
stopped by Pr.02.02.
When operation command source is external terminal, the keypad
cannot be used to change PLC status. And this function will be
invalid when AC Motor drive is in PLC2 status.
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11