Over-Torque Detection Mode (Ol2); Over-Torque Detection Level (Ol2); Over-Torque Detection Time (Ol2) - Delta Electronics AC Motor Drive VFD-E User Manual

Vfd-e high performance/flexible options/micro type ac motor drives
Table of Contents

Advertisement

Chapter 4 Parameters|
06.03

Over-Torque Detection Mode (OL2)

Settings
This parameter determines the operation mode of the drive after the over-torque (OL2) is
detected via the following method: if the output current exceeds the over-torque detection level
(Pr.06.04) longer than the setting of Pr.06.05 Over-Torque Detection Time, the warning
message "OL2" is displayed. If a Multi-functional Output Terminal is set to over-torque
detection (Pr.03.00~03.01=04), the output is on. Please refer to Pr.03.00~03.01 for details.
06.04

Over-Torque Detection Level (OL2)

Settings
This setting is proportional to the Rated Output Current of the drive.
06.05

Over-Torque Detection Time (OL2)

Settings
4-92
Over-Current
Detection
Level
06.02
over-current stall prevention during operation
0
Over-Torque detection disabled.
1
Over-Torque detection enabled during constant speed operation.
After over-torque is detected, keep running until OL1 or OL occurs.
2
Over-Torque detection enabled during constant speed operation.
After over-torque is detected, stop running.
3
Over-Torque detection enabled during acceleration. After over-
torque is detected, keep running until OL1 or OL occurs.
4
Over-Torque detection enabled during acceleration. After over-
torque is detected, stop running.
10 to 200%
0.1 to 60.0 sec
Over-Current Stall
Prevention during
Operation, output
frequency decrease
Output
Frequency
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
Output Current
Factory Setting: 0
Factory Setting: 150
Factory Setting: 0.1
Unit: 1
Unit: 0.1