Appendix D How to Use PLC Function|
Counter
Coils driven up by the OUT
command
Devices driven up by the
SET and RST commands
Application commands
2.
MCR is the main-control ending command that is placed at the end of the main-control
program and there should not be any contact commands prior to the MCR command.
3.
Commands of the MC-MCR main-control program supports the nest program structure,
with 8 layers as its greatest. Please use the commands in order from N0~ N7, and refer to
the following:
Program Example:
Ladder diagram:
X0
X1
X2
X3
MCR
MCR
X10
X11
MCR
D-40
The coil is OFF, and the counting value and the contact stay at
their present condition
All turned OFF
Stay at present condition
All of them are not acted , but the nest loop FOR-NEXT
command will still be executed for times defined by users even
though the MC-MCR commands is OFF.
MC
N0
Y0
MC
N1
Y1
N1
N0
MC
N0
Y10
N0
Command code: Operation:
LD
X0
Load A contact of X0
MC
N0
Enable N0 common series
connection contact
LD
X1
Load A contact of X1
OUT
Y0
Drive Y0 coil
:
LD
X2
Load A contact of X2
MC
N1
Enable N1 common series
connection contact
LD
X3
Load A contact of X3
OUT
Y1
Drive Y1 coil
:
MCR
N1
Disable N1 common series
connection contact
:
MCR
N0
Disable N0 common series
connection contact
:
LD
X10
Load A contact of X10
MC
N0
Enable N0 common series
connection contact